background image

 

Note: 

A higher number of heating cycles per hour 

results in more accurate temperature control, but could 
accelerate the wear of mechanical components in the 
equipment. 

To set the maximum number of heating cycles per 
hour while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the heating cycles 

per hour prompt appears in the display. Press 
YES to enter the heating cycles per hour menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

maximum number of heating cycles per hour. 
Press YES to store the value. 

The display now shows the cooling cycles per hour 
setup prompt. See the 

Setting the Maximum Cooling 

Stage Cycles per Hour (Cool cph)

 section for 

instructions. 

Setting the Maximum Cooling Stage Cycles per 
Hour (Cool cph) 

The cooling cycles per hour establishes the maximum 
number of times the equipment or stages are turned 
on and off in one hour. The selection ranges from 
three to four cycles per hour. 

Note: 

A higher number of cooling cycles per hour 

results in more accurate temperature control, but could 
accelerate the wear of mechanical components in the 
equipment. 

To set the maximum number of cooling cycles per 
hour while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the cooling cycles 

per hour prompt appears in the display. Press 
YES to enter the cooling cycles per hour menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

maximum number of cooling cycles per hour. 
Press YES to store the value. 

The display now shows the minimum heating/cooling 
deadband prompt. See the 

Setting the Heating/Cooling 

Deadband (Deadband)

 section for instructions. 

Setting the Heating/Cooling Deadband (Deadband) 

The heating/cooling deadband setting establishes the 
minimum difference between the heating and cooling 
setpoints. The range is adjustable from 2 to 4 F

°

 

(1 to 2 C

°

). 

To change the minimum deadband between the 
heating and cooling setpoints while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the deadband 

setpoint prompt appears in the display. Press YES 
to enter the deadband setpoint menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

minimum deadband between the heating and 
cooling setpoints. Press YES to store the value. 

The display now shows the fan control prompt. See 
the 

Setting the Fan Control (Fan cont) 

section for 

instructions. 

Setting the Fan Control (Fan cont) 

This parameter controls how the fan activates in 
response to a call for heating. 

When the fan is in Auto Mode (as selected on the Main 
User Menu): 

• 

Select 

on

 to enable the thermostat to control the 

fan on a call for heating or cooling. 

• 

Select 

off

 to energize the fan on a call for cooling 

only by the thermostat. On a call for heating, the 
fan is controlled by the equipment fan limit control. 

To set the fan control while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the fan control 

prompt appears in the display. Press YES to enter 
the Fan Control Menu. 

2.  Using the UP/DOWN arrow keys, select 

on

 or 

off

Press YES to store the selection. 

The display now shows the fan delay prompt. See the 

Setting the Fan Delay (Fan del)

 section for 

instructions. 

Setting the Fan Delay (Fan del) 

The fan delay extends the fan operation by 
60 seconds after the call for heating or cooling has 
ended. This feature is only active when the fan is in 
the 

Auto

 mode. 

To enable the fan delay while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the fan delay 

prompt appears in the display. Press YES to enter 
the Fan Delay Menu. 

2.  Using the UP/DOWN arrow keys, select 

on

 or 

off

Press YES to store the selection. 

The display now shows the N2 address prompt. See 
the 

Setting the N2 Address (N2 addr)

 section for 

instructions. 

TEC2104-1 Networked Multi-Stage Economizer Thermostat Installation Instructions    

11

 

Summary of Contents for TEC2104-1

Page 1: ...side doors away from steam or water pipes warm air stacks unheated uncooled areas or sources of electrical interference To install the thermostat 1 Remove the security screw on the bottom of the therm...

Page 2: ...the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the TEC2104 1 wiring diagram Figure 5 2 Gently push excess wire back into the wall plug the wall h...

Page 3: ...C N2 N2 REF Terminal OS D2 Scom RS D1 Remote Room Sensor OS REF N2 N2 Auxiliary Outdoor Sensor N2 N2 REF Metasys CPN NCM EC 0 to 10 VDC 24 VAC Common MS EC Remote Mixed Air Sensor Cool 2 fig5 b Figure...

Page 4: ...o 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP a ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP A...

Page 5: ...System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode On at the TEC keypad the TEC keeps the System Mode Off Once an over...

Page 6: ...to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manually scroll to the next parameter on the menu adjust values Note When left una...

Page 7: ...t pressing the YES key To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds it reverts to the Sta...

Page 8: ...tages See the Disable Enable Second Cooling Stage C Stage section Disables Heating Operation based on Auxiliary Outdoor Air Temperature Default 120 F 49 C See the Setting the Heating Lockout H lock se...

Page 9: ...the TEC2104 1 the states of DI1 and DI2 are communicated over the N2 network This enables the ability to communicate alarm conditions over the network without local annunciation on the TEC2104 1 displ...

Page 10: ...F 12 to 37 5 C Note When adjusting the temperature holding the keys down changes the temperature by 5 F C increments To set the minimum cooling setpoint while in the Installer Configuration Menu 1 Ans...

Page 11: ...stable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in the Installer Configuration Menu 1 Answer NO to all prompts until the deadband setpoint...

Page 12: ...offset while in the Installer Configuration Menu 1 Answer NO to all prompts until the room sensor calibration prompt appears in the display Press YES to enter the Room Sensor Calibration Menu 2 Use th...

Page 13: ...F C To change the outdoor air temperature cooling lockout while in the Installer Configuration Menu 1 Answer NO to all prompts until the cooling lockout prompt appears in the display Press YES to ent...

Page 14: ...djust the mixed air setpoint Press YES to store the temperature The display mixed air temperature prompt is now displayed See the Displaying the Mixed Air Temperature Display section for instructions...

Page 15: ...tered It is also where any temporary setpoints are entered To enter the heating and cooling setpoints for the occupied and unoccupied modes permanent or temporary follow the steps in Table 4 When chan...

Page 16: ...set temperature Press YES to store value and advance to the next menu Press YES to change the unoccupied heating setpoint Press NO to advance to temperature display units Use the UP DOWN arrow keys t...

Page 17: ...all prompts until the system mode prompt appears in the display Press YES to set the system mode 1 Answer NO to all prompts until the fan mode prompt appears in the display Press YES to set the fan m...

Page 18: ...ine Device type is incorrect TEC2104 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed Install EOL jumpers properly MM CVT101 is not plugged into the Personal Compute...

Page 19: ...ompliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide...

Reviews: