Disable/Enable Second Cooling Stage (C Stage) 

This parameter reverts the operation of two-stage 
thermostats to a single stage when the second cooling 
stage is not needed. 

To enable or disable the second cooling stage while in 
the Installer Configuration Menu: 

1.  Answer NO to all prompts until the setting cooling 

stages prompt appears in the display. Press YES 
to enter the Setting Cooling Stages Menu. 

2.  Using the UP/DOWN arrow keys, select 

1.0

 or 

2.0

 

stages. Press YES to store the selection. 

The display now shows the heating lockout prompt. 
See the 

Setting the Heating Lockout (H lock)

 section 

for instructions. 

Setting the Heating Lockout (H lock) 

This feature disables heating operation based on 
auxiliary or outdoor air temperature (requires 
temperature sensor to be connected to the 
Auxiliary/Outdoor Air Sensor terminal OS for the 
function to be enabled [Figure 5]). If the outdoor air 
temperature is above the heating lockout temperature, 
heating operation is disabled. 

The heating lockout temperature parameter is 
adjustable from -15 to 123

°

F (-26 to 51

°

C) in 

increments of 5 F/C

°

Note: 

Setting the heating lockout above 122

°

(50

°

C) disables the heating lockout feature. The 

maximum temperature displayed is 122

°

F (50

°

C). 

To change the outdoor air temperature-heating lockout 
while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the heating lockout 

prompt appears in the display. Press YES to enter 
the Heating Lockout Menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

lockout temperature. Press YES to store the value. 

The display now shows the cooling lockout prompt. 
See the 

Setting the Cooling Lockout (C lock)

 section 

for instructions. 

Setting the Cooling Lockout (C lock) 

This feature disables cooling operation based on 
outdoor air temperature (requires outdoor air 
temperature sensor to be connected for the function to 
be enabled). If the outdoor air temperature is below 
the cooling lockout temperature, cooling operation is 
disabled. 

The cooling lockout temperature parameter is 
adjustable from -40 to 95

°

F (-40 to 35

°

C) in increments 

of 5 F/C

°

To change the outdoor air temperature-cooling lockout 
while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the cooling lockout 

prompt appears in the display. Press YES to enter 
the Cooling Lockout Menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

lockout temperature. Press YES to store the value. 

The display now shows the Economizer Changeover 
Setpoint Menu. See the 

Setting the

 

Economizer 

Changeover Temperature (Chngstpt)

 section for 

instructions. 

Setting the Economizer Changeover Temperature 
(Chngstpt) 

The TEC2104-1 economizer changeover strategy is 
based on outdoor air temperature (requires outdoor air 
temperature sensor). When the outdoor air 
temperature is below the changeover setpoint, free 
cooling is used (economizer). When the outdoor air 
temperature is above the setpoint, mechanical cooling 
is used (compressor). 

To adjust the changeover setpoint while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the economizer 

changeover setpoint prompt appears in the 
display. Press YES to enter the Changeover 
Setpoint Menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

economizer changeover temperature. Press YES 
to store the value. 

The display now shows the Outside Damper Minimum 
Position Menu. See the 

Setting the Outdoor Air 

Damper Minimum Position (Min pos) 

section for 

instructions. 

Setting the Outdoor Air Damper Minimum Position 
(Min pos) 

The minimum position for the outdoor air dampers on 
the economizer can be adjusted as necessary. The 
dampers are energized to minimum position when the 
fan (G terminal) is energized and the thermostat is in 
the occupied mode. When the schedule is in the 
unoccupied mode, the minimum position is 0%. 

To set the minimum position for the outdoor air 
dampers while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the minimum 

position setpoint prompt appears in the display. 
Press YES to enter the Minimum Position Menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

minimum position for the outdoor air damper. 
Press YES to store the value. 

The display now shows the Mechanical Cooling Mode 
Menu. See the 

Setting the Mechanical Cooling Mode 

(C mech)

 section for instructions. 

TEC2104-1 Networked Multi-Stage Economizer Thermostat Installation Instructions    

13

 

Summary of Contents for TEC2104-1

Page 1: ...side doors away from steam or water pipes warm air stacks unheated uncooled areas or sources of electrical interference To install the thermostat 1 Remove the security screw on the bottom of the therm...

Page 2: ...the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the TEC2104 1 wiring diagram Figure 5 2 Gently push excess wire back into the wall plug the wall h...

Page 3: ...C N2 N2 REF Terminal OS D2 Scom RS D1 Remote Room Sensor OS REF N2 N2 Auxiliary Outdoor Sensor N2 N2 REF Metasys CPN NCM EC 0 to 10 VDC 24 VAC Common MS EC Remote Mixed Air Sensor Cool 2 fig5 b Figure...

Page 4: ...o 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP a ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP A...

Page 5: ...System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode On at the TEC keypad the TEC keeps the System Mode Off Once an over...

Page 6: ...to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manually scroll to the next parameter on the menu adjust values Note When left una...

Page 7: ...t pressing the YES key To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds it reverts to the Sta...

Page 8: ...tages See the Disable Enable Second Cooling Stage C Stage section Disables Heating Operation based on Auxiliary Outdoor Air Temperature Default 120 F 49 C See the Setting the Heating Lockout H lock se...

Page 9: ...the TEC2104 1 the states of DI1 and DI2 are communicated over the N2 network This enables the ability to communicate alarm conditions over the network without local annunciation on the TEC2104 1 displ...

Page 10: ...F 12 to 37 5 C Note When adjusting the temperature holding the keys down changes the temperature by 5 F C increments To set the minimum cooling setpoint while in the Installer Configuration Menu 1 Ans...

Page 11: ...stable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in the Installer Configuration Menu 1 Answer NO to all prompts until the deadband setpoint...

Page 12: ...offset while in the Installer Configuration Menu 1 Answer NO to all prompts until the room sensor calibration prompt appears in the display Press YES to enter the Room Sensor Calibration Menu 2 Use th...

Page 13: ...F C To change the outdoor air temperature cooling lockout while in the Installer Configuration Menu 1 Answer NO to all prompts until the cooling lockout prompt appears in the display Press YES to ent...

Page 14: ...djust the mixed air setpoint Press YES to store the temperature The display mixed air temperature prompt is now displayed See the Displaying the Mixed Air Temperature Display section for instructions...

Page 15: ...tered It is also where any temporary setpoints are entered To enter the heating and cooling setpoints for the occupied and unoccupied modes permanent or temporary follow the steps in Table 4 When chan...

Page 16: ...set temperature Press YES to store value and advance to the next menu Press YES to change the unoccupied heating setpoint Press NO to advance to temperature display units Use the UP DOWN arrow keys t...

Page 17: ...all prompts until the system mode prompt appears in the display Press YES to set the system mode 1 Answer NO to all prompts until the fan mode prompt appears in the display Press YES to set the fan m...

Page 18: ...ine Device type is incorrect TEC2104 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed Install EOL jumpers properly MM CVT101 is not plugged into the Personal Compute...

Page 19: ...ompliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide...

Reviews: