Setting the N2 Address (N2 addr)
To adjust the N2 address (adjustable from 1 to 253)
while in the Installer Configuration Menu:
1. Answer NO to all prompts until the setting the N2
address prompt appears in the display. Press YES
to set the address.
2. Use the UP/DOWN arrow keys to display the
desired address. Press YES to store the address.
The display now shows the temporary occupancy
override time prompt. See the
Establishing the
Temporary Occupancy Time (ToccTime)
section for
instructions.
Note:
Pressing the YES and NO keys
simultaneously for 5 seconds on the user interface of
the TEC2104-1 temporarily displays the N2 address of
the thermostat.
Establishing the Temporary Occupancy Time
(ToccTime)
The temporary occupancy is the length of time the
occupied mode setpoints are used when the override
function is enabled (the override function can be
enabled from the Main User Menu
when the
thermostat is in unoccupied mode
or from one of
the digital inputs) or a temporary setpoint is entered.
The range is adjustable from 0 to 12 hours.
To change the temporary occupancy time while in the
Installer Configuration Menu:
1. Answer NO to all prompts until the temporary
occupancy time prompt appears in the display.
Press YES to enter the temporary occupancy time
menu.
2. Use the UP/DOWN arrow keys to adjust the length
of time the temporary occupancy setpoint should
be in effect. Press YES to store the time.
The display now shows the room sensor calibration
prompt. See the
Room Air Sensor Calibration (Cal RS)
section for instructions.
Room Air Sensor Calibration (Cal RS)
An offset can be added or subtracted to the actual
displayed room temperature as needed. The range is
±
5.0 F
°
(
±
2.5 C
°
), adjustable in increments of 1 F
°
(0.5 C
°
).
To change the room sensor calibration/offset while in
the Installer Configuration Menu:
1. Answer NO to all prompts until the room sensor
calibration prompt appears in the display. Press
YES to enter the Room Sensor Calibration Menu.
2. Use the UP/DOWN arrow keys to adjust the
correction that should be applied to the sensor
reading. Press YES to store the offset.
The display now shows the auxiliary
temperature/outdoor air sensor calibration prompt.
See the
Auxiliary Temperature/Outdoor Air Sensor
Calibration (Cal OS)
section for instructions.
Auxiliary Temperature/Outdoor Air Sensor
Calibration (Cal OS)
An offset can be added or subtracted to the actual
displayed auxiliary/outdoor air temperature as needed.
The range is
±
5.0 F
°
(
±
2.5 C
°
), adjustable in
increments of 1 F
°
(0.5 C
°
).
To change the sensor calibration/offset while in the
Installer Configuration Menu:
1. Answer NO to all prompts until the
auxiliary/outdoor sensor calibration prompt
appears in the display. Press YES to enter the
Auxiliary/Outdoor Sensor Calibration Menu.
2. Use the UP/DOWN arrow keys to adjust the
correction that should be applied to the sensor
reading. Press YES to store the offset.
The display now shows the heating stage setting
prompt. See the
Disable/Enable Second Heating
Stage (H Stage)
section for instructions.
Disable/Enable Second Heating Stage (H Stage)
This parameter reverts the operation of two stage
thermostats to a single stage when the second heating
stage is not needed.
To enable or disable the second heating stage while in
the Installer Configuration Menu:
1. Answer NO to all prompts until the setting heating
stages prompt appears in the display. Press YES
to enter the Setting Heating Stages Menu.
2. Using the UP/DOWN arrow keys; select
1.0
or
2.0
stages. Press YES to store the selection.
The display now shows the cooling stage setting
prompt. See the
Disable/Enable Second Cooling
Stage (C
Stage)
section for instructions.
12
TEC2104-1 Networked Multi-Stage Economizer Thermostat Installation Instructions