Table 1: N2 Bus Objects
Point Name
TEC Point
Type/
Address
N30/NAE
Object
Type
BAS Model
Point Type
Override Range
Room Temp
a
ADI-1 N2
AI CSAD 32 to 122
°
F (0 to 50
°
C)
Aux Temp/Outdoor Temp
a
ADI-2 N2
AI CSAD -40 to 122
°
F (-40 to 50
°
C)
Heating SP
a, g
(Occupied Heating SP)
ADI-3 N2
AO CSAD 40 to 90
°
F (4.5 to 32
°
C)
Cooling SP
a, g
(Occupied Cooling SP)
ADI-4 N2
AO CSAD 54 to 100
°
F (12 to 37.5
°
C)
Setback Heating SP
a, g
(Unoccupied Heating SP)
ADI-5 N2
AO CSAD 40 to 90
°
F (4.5 to 32
°
C)
Setback Cooling SP
a, g
(Unoccupied Cooling SP)
ADI-6 N2
AO CSAD 54 to 100
°
F (12 to 37.5
°
C)
Minimum Heat SP
ADI-7 N2
AI CSAD 40
°
F (4.5
°
C)
Maximum Heat SP
a
ADI-8 N2
AO CSAD 40 to 90
°
F (4.5 to 32
°
C)
Minimum Cool SP
a
ADI-9 N2
AO CSAD 54 to 100
°
F (12 to 37.5
°
C)
Maximum Cool SP
ADI-10 N2
AI CSAD 100
°
F (37.5
°
C)
Fan
a
BD-1
N2 BO
CSBD
0 = Auto, 1 = On
Mode
a
BD-2 N2
MSO
d, e
CSMS
0 = Off, 1 = Cool, 2 = Heat, 3 = Auto
Occupancy
a
BD-3
N2 BO
CSBD
0 = Unoccupied, 1 = Occupied
W1 State
BD-4
N2 BI
CSBD
0 = Off, 1 = On
W2 State
BD-5
N2 BI
CSBD
0 = Off, 1 = On
Y1 State
BD-6
N2 BI
CSBD
0 = Off, 1 = On
Y2 State
BD-7
N2 BI
CSBD
0 = Off, 1 = On
G State – Fan
BD-8
N2 BI
CSBD
0 = Off, 1 = On
Temp Units
a, c
(Local Display Only)
BD-9 N2
BO
See
Footnote c.
0 =
°
C, 1 =
°
F
Continued on the next page . . .
4
TEC2104-1 Networked Multi-Stage Economizer Thermostat Installation Instructions