background image

 

Technical Specifications 

Product 

TEC2104-1 Thermostat with N2 Bus, Multi-Stage with Economizer Control 

Power Requirements 

20-30 VAC, 50/60 Hz, 24 VAC nominal, 2 VA (RC and C) Class 2 

Relay Contact Rating 
Maximum Inductive 

1 ampere with in-rush surges up to 3 amperes, 30 VAC maximum, Class 2 

Digital Inputs 

Relay dry contact only across the C terminal to DI1 or DI2 

Economizer Output 

0 to 10 VDC into 2 K ohm resistance minimum 

Recommended Wire Size 

18 gauge maximum, 22 gauge recommended 

Thermostat Measurement 
Range 

-40 to 122

°

F (-40 to 50

°

C) 

Sensor Type: 
Resolution: 
Control Accuracy: 

Local 10 K ohm NTC thermistor 

±

 0.2F

°

 (

±

 0.1C

°

±

 0.9F

°

 (

±

 0.5C

°

) @ 70

°

F (21

°

C) typical calibrated 

Auxiliary/Outdoor Air 
Temperature Indication 
Range 

-40 to 122

°

F (-40 to 50

°

C) 

Control Range 

Cooling: 54 to 100

°

F

 (

12 to 37.5

°

C) in 1/2 degree increments 

Heating: 40 to 90

°

F (4.5 to 32

°

C) in 1/2 degree increments

 

Minimum Deadband 

(Between heating and cooling) 2F

°

 or 1C

°

 

Ambient Operating 
Conditions 

32 to 122

°

F (0 to 50

°

C); 0 to 95% RH noncondensing 

Ambient Storage 
Conditions 

-22 to 122

°

F (-30 to 50

°

C); 0% to 95% RH noncondensing 

Dimensions (H x W x D) 

4.92 in. x 3.36 in. x 1.13 in. (125 x 86 x 29 mm) 

Shipping Weight 

0.75 lb (0.34 kg) 

UL and cUL Listing 

File E27734 with CCN’s XAPX (US, UL 873) and XAPX7 (Canada, CSA C22.2 No. 24) 

CE Compliance 

CE Directives EN50081-1: 1992 EMC Emission; EN50082-2 EMC Immunity (Pending) 

FCC Compliance 

This equipment has been tested and found to comply with the limits for a Class A digital 
device and verified to Class B pursuant to Part 15 of FCC Rules. These limits are designed 
to provide reasonable protection against harmful interference when this equipment is 
operated in a commercial environment. This equipment generates, uses, and can radiate 
radio frequency energy and, if not installed and used in accordance with the instruction 
manual, may cause harmful interference to radio communications. 

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these 
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or 
misuse of its products. 

This device complies with Class A Part 15 of the FCC rules. It was also verified to Class B. Operation is subject to 
the following two conditions: 
(1) This device may not cause harmful interference. 
(2) This device must accept any interference received, including interference that may cause undesired operation. 
This Class A digital apparatus meets all of the requirements of the Canadian Interference-Causing Equipment 
Regulations. Cet appareil numérique de la Classe A respecte toutes les exigences du Règlement sur le materiél 
brouilleur du Canada. 

Controls Group 

507 E. Michigan Street 
P.O. Box 423 

Published in U.S.A.

Milwaukee, WI  53201 

www.johnsoncontrols.com

TEC2104-1 Networked Multi-Stage Economizer Thermostat Installation Instructions    

19

 

Summary of Contents for TEC2104-1

Page 1: ...side doors away from steam or water pipes warm air stacks unheated uncooled areas or sources of electrical interference To install the thermostat 1 Remove the security screw on the bottom of the therm...

Page 2: ...the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the TEC2104 1 wiring diagram Figure 5 2 Gently push excess wire back into the wall plug the wall h...

Page 3: ...C N2 N2 REF Terminal OS D2 Scom RS D1 Remote Room Sensor OS REF N2 N2 Auxiliary Outdoor Sensor N2 N2 REF Metasys CPN NCM EC 0 to 10 VDC 24 VAC Common MS EC Remote Mixed Air Sensor Cool 2 fig5 b Figure...

Page 4: ...o 100 F 12 to 37 5 C Minimum Heat SP ADI 7 N2 AI CSAD 40 F 4 5 C Maximum Heat SP a ADI 8 N2 AO CSAD 40 to 90 F 4 5 to 32 C Minimum Cool SP a ADI 9 N2 AO CSAD 54 to 100 F 12 to 37 5 C Maximum Cool SP A...

Page 5: ...System Mode On However if the Metasys system sends an override command to turn System Mode Off then the occupant selects System Mode On at the TEC keypad the TEC keeps the System Mode Off Once an over...

Page 6: ...to scroll through menu selections or adjust values up arrow SCROLL key to stop the Status Display Menu from scrolling manually scroll to the next parameter on the menu adjust values Note When left una...

Page 7: ...t pressing the YES key To pass over a parameter without changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds it reverts to the Sta...

Page 8: ...tages See the Disable Enable Second Cooling Stage C Stage section Disables Heating Operation based on Auxiliary Outdoor Air Temperature Default 120 F 49 C See the Setting the Heating Lockout H lock se...

Page 9: ...the TEC2104 1 the states of DI1 and DI2 are communicated over the N2 network This enables the ability to communicate alarm conditions over the network without local annunciation on the TEC2104 1 displ...

Page 10: ...F 12 to 37 5 C Note When adjusting the temperature holding the keys down changes the temperature by 5 F C increments To set the minimum cooling setpoint while in the Installer Configuration Menu 1 Ans...

Page 11: ...stable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in the Installer Configuration Menu 1 Answer NO to all prompts until the deadband setpoint...

Page 12: ...offset while in the Installer Configuration Menu 1 Answer NO to all prompts until the room sensor calibration prompt appears in the display Press YES to enter the Room Sensor Calibration Menu 2 Use th...

Page 13: ...F C To change the outdoor air temperature cooling lockout while in the Installer Configuration Menu 1 Answer NO to all prompts until the cooling lockout prompt appears in the display Press YES to ent...

Page 14: ...djust the mixed air setpoint Press YES to store the temperature The display mixed air temperature prompt is now displayed See the Displaying the Mixed Air Temperature Display section for instructions...

Page 15: ...tered It is also where any temporary setpoints are entered To enter the heating and cooling setpoints for the occupied and unoccupied modes permanent or temporary follow the steps in Table 4 When chan...

Page 16: ...set temperature Press YES to store value and advance to the next menu Press YES to change the unoccupied heating setpoint Press NO to advance to temperature display units Use the UP DOWN arrow keys t...

Page 17: ...all prompts until the system mode prompt appears in the display Press YES to set the system mode 1 Answer NO to all prompts until the fan mode prompt appears in the display Press YES to set the fan m...

Page 18: ...ine Device type is incorrect TEC2104 1 address must be VND device type EOL jumpers on MM CVT101 or NCM are not installed Install EOL jumpers properly MM CVT101 is not plugged into the Personal Compute...

Page 19: ...ompliance This equipment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide...

Reviews: