LX Series Unit Ventilator Controller User's Guide
95
nvoUVstate
This network variable output sends the unit ventilator status. It provides the
configuration errors and mode status.
Type: SNVT_state_64 (165)
Format: UNVT_uv_state
HighCO2Level
48
The CO
2
concentration is higher than the CO
2
limit
by more than the amount defined in any CO
2
offset
and for longer than the time defined in the alarm
delay.
FanStateMismatch
49
The fan state is different than the fan output for a
time period longer than the alarm delay.
AuxiliaryLowAlarm
50
The auxiliary alarm input is lower than the low limit
setpoint for a time period longer than the alarm
delay.
AuxiliaryHighAlarm
51
The auxiliary alarm input is higher than the low limit
setpoint for a time period longer than the alarm
delay.
Emergency
52
The Heat Pump Unit Controller is in emergency
mode.
Table 32: nvoHPstate (Part 1 of 2)
Programmatic Name
Bit
Number
Meaning When Bit Is Set
OutofService
0
The device is out of service. There is no space
temperature sensor configured, or nvislave is not
bound.
EmergencyMode
1
Emergency mode is ON. It is received from the
nviEmergCmd or sent by the emergency contact.
HotWater
2
The water is hot.
EconomizerEnabled
3
Economizer is enabled. This occurs when the
outdoor temperature is lower than the economizer
maximum outdoor temperature.
MecCoolingEnabled
4
Mechanical cooling is enabled. This occurs when
the outdoor temperature is higher than the
mechanical minimum outdoor temperature.
CtrlOutputxOverridden
8–14
The unit ventilator object output is overridden.
HwOutputxOverridden
15–21
The hardware output is overridden.
DupReturnTempCfgError
36
Duplicate return air temperature sensor
configuration error.
DupDischrgTempCfgError
37
Duplicate discharge air temperature sensor
configuration error.
DupOutTempTempCfgError
38
Duplicate outdoor air temperature sensor
configuration error.
DupMixAirTempCfgError
39
Duplicate mixed air temperature sensor
configuration error.
DupWaterTempCfgError
40
Duplicate water temperature sensor configuration
error.
Table 31: nvoUValarm (Part 3 of 3)
Programmatic Name
Bit
Number
Meaning When Bit Is Set