LX Series Unit Ventilator Controller User's Guide
65
Disconnect Alarms
The column heading Bit # refers to the Bit Number of nvoUValarm. The column
programmatic name refers to the programmatic name of nvoUValarm with the
format type UNVT_uv_alarm that relays the status of the object. If a heartbeat
alarm comes ON, an electrical fault alarm sounds. The Bit #11 of nvoStatus,
programmatic name electrical_fault, turns ON. Table 12 describes disconnect
alarms.
Emergency Mode Alarms
Emergency mode is described in the
section. Emergency
mode alarm begins when the emergency mode begins. In Table 13, the column
programmatic name refers to the programmatic name of nvoUValarm with the
format type UNVT_uv_alarm, which relays the status of the object.
User-Set Alarms
The column heading Bit # refers to the Bit Number of nvoUValarm. The column
programmatic name refers to the programmatic name of nvoUValarm with the
format type UNVT_rt_alarm that relays the status of the object. If a user-set alarm
comes ON, an out of limits alarm sounds. The Bit #4 of nvoStatus, programmatic
name out_of_limits, turns ON.
Table 12: Disconnect Alarms
Sensor
Time
Disconnected
Bit #
Programmatic Name
Space Temperature
Sensor
30 seconds
32
SpaceTempSensorFault
Discharge Air Temperature
Sensor
30 seconds
33
DischargeTempSensorFault
Return Air Temperature
Sensor
30 seconds
34
ReturnTempSensorFault
Mixed Air Temperature
Sensor
30 seconds
35
MixedAirTempSensor
Outdoor Air Temperature
Sensor
30 seconds
36
OutdoorTempSensor
Water Temperature Sensor
30 seconds
37
WaterTempSensorFault
Setpoint Offset
30 seconds
38
SetpointOffsetElecFault
Table 13: Emergency Mode Alarm
Monitored State
Bit #
Programmatic Name
Emergency Mode
48
Emergency