LX Series Unit Ventilator Controller User's Guide
105
Table 48: SNVT_switch Input Network Variable
Value (raw)
State
Two-State Interpretation
Any
0
Off (0; 0)
0
1
Off (0; 1)
> 0
1
On (200; 1)
Any
-1 (0xFF)
Invalid (no action)
Table 49: SNVT_switch Output Network Variable
Value (raw)
State
Two-State Interpretation
0
0
Off
200 (0xC8)
1
On
0 – 200
(0xC8) (any valid value)
-1
(0xFF)
Invalid (NULL)
Table 50: SNVT_switch Value
SNVT_switch Value
Description
Field
Value
Measurement
Value
Field Type Category
Unsigned Short
Type Size
1 byte
Valid Type Range
0 – 100
Type Resolution
0.5
Units
Percent of full scale
Invalid Value
N/A
Raw Range
0 – 100
(0 – 0xC8)
Scale Factor
5, -1, 0
S = a*10
b
*(R+c)
File Name
N/A
Default Value
N/A
Table 51: SNVT_switch State
SNVT_switch State
Description
Field
State
Measurement
State
Field Type Category
Signed Short
Type Size
1 byte
Valid Type Range
0-1
Type Resolution
1
Units
N/A
Invalid Value
-1 (0xFF)
Raw Range
0-1
Scale Factor
1, 0, 0
S = a*10
b
*(R+c)
File Name
N/A
Default Value
N/A