LX Series Unit Ventilator Controller User's Guide
81
Options Configuration
On the Options Configuration screen (Figure 37) you can perform the following
tasks:
•
Configure Optimum Start
•
Configure Humidity Control
•
Enable Frost Protection
Optimum Start
Optimum Start prepares the space for occupancy in advance of the occupied
period. The UVC uses stored daily statistics to calculate the length of time required
each day to reach the occupied setpoints just as actual occupancy begins.
Optimum Start is described in the
section.
Note:
For Optimum Start to work, the network variable nviOccCmd must be set
to SNVT type SNVT_tod_event. Use the Changeable Nv Manager view of
the device in FX Workbench to change the SNVT type.
Figure 37: Options Configuration Screen