LX Series Unit Ventilator Controller User's Guide
90
nviHotWater
This network variable input receives the water state. Water state refers to whether
the water is hot or cold.
When state and value are not set to zero, the water state is hot. When state or value
is set to zero, the water state is cold.
Type: SNVT_switch (95)
nviMixedAirTemp
Used to receive the mixed air temperature. Network values have priority over local
sensor values.
Type: SNVT_occupancy (109) or SNVT_tod_event (128)
nviOccCmd and nviOccManCmd
This network variable input is used to command the Unit Ventilator Controller
object into different occupancy modes. See the
information. Table 30 shows the possible values of nviOccCmd and
nviOccManCmd.
Type: SNVT_occupancy (109) or SNVT_tod_event (128)
The network variable nviOccCmd commands the Unit Ventilator Unit Controller
to change modes according to the value of the variable. The value of nviOccCmd
itself can be changed by a network schedule or a manual change.
While in any mode, the UVC can enter a heating or cooling state as required to
maintain the space within the limits of the setpoints.
nviOutdoorEnth
Used to receive the outdoor enthalpy. Network values have priority over local
sensor values.
Type: SNVT_enthalpy (153)
nviOutdoorRH
Used to receive the outdoor air humidity. Network values have priority over local
sensor values.
Type: SNVT_lev_percent (81)
Table 30: Values of nviOccCmd and Modes
Value
Identifier
Unit Ventilator Controller Mode
0
OC_OCCUPIED
Occupied Mode
1
OC_UNOCCUPIED
Unoccupied mode
2
OC_BYPASS
Bypass mode
3
OC_STANDBY
Standby mode
0xFF
OC_NUL
Invalid data