8
7
6
5
4
3
2
MODEL No.
J
DHX4852
N
Power source
208 - 230 V / 1ø / 60 Hz
Controller P.C.B. Ass'y
CR-UHX0762 (Microprocessor)
Fan...(Number diameter / length in. (mm))
Centrifugal (1 ... ø7-31/64 (ø220))
Fan motor
Model...Nominal output
W
KFC4Q-401A6P...400W
Power source
208 - 230 V / 1ø / 60 Hz
No. of pole...r.p.m. (230V, High)
rpm
4P... 1,077
Coil resistance
(Ambient temperature 68°F)
WHT – BRN : 11.05
WHT – VLT : 1.796
VLT – ORG : 1.002
ORG – YEL : 4.574
YEL – PNK : 7.699
Run capacitor
VAC, μF
440 VAC, 7.0 μF
Safety device
fuse
Operating temperature
Open °F (°C)
266 ± 9 (130 ± 5)
Close °F (°C)
181 ± 27 (83 ± 15)
Electronic expansion valve
Coil
UKV-U030E
Coil resistance (at 68°F)
ORG – GRY : 46
YEL – GRY : 46
RED – GRY : 46
BLK – GRY : 46
Valve body
UKV-30D33
Heat exchanger
Coil
Aluminum plate fin / Copper tube
Rows...fi n pitch
in. (mm)
4...5 / 64 (2.0)
Face area
ft
2
(m
2
)
3.02 (0.281)
TD831149-00̲3WAY.indb 88
2010/01/26 15:11:17
FORM 121.00-EG1
ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
98
Concealed Duct High Static Pressure (JD Type)
Indoor unit (B)
Summary of Contents for JA Series
Page 181: ...Schematic Diagram JDHX3652N FORM 121 00 EG1 ISSUE DATE 5 31 2012 181 JOHNSON CONTROLS ...
Page 183: ...Schematic Diagram JDHX4852N FORM 121 00 EG1 ISSUE DATE 5 31 2012 183 JOHNSON CONTROLS ...
Page 189: ...Schematic Diagram JKHX1862N FORM 121 00 EG1 ISSUE DATE 5 31 2012 189 JOHNSON CONTROLS ...
Page 191: ...Schematic Diagram JKHX2452N FORM 121 00 EG1 ISSUE DATE 5 31 2012 191 JOHNSON CONTROLS ...