![Johnson Controls JA Series Engineering Manual Download Page 128](http://html.mh-extra.com/html/johnson-controls/ja-series/ja-series_engineering-manual_2023361128.webp)
8
7
6
5
4
3
2
1
Unit specifi cations (D)
MODEL No.
Indoor Unit
J
FHX1562
N
POWER SOURCE
208 - 230 V / 1ø / 60 Hz
PERFORMANCE
Cooling
Heating
Capacity
BTU / h
15,000
17,000
kW
4.5
5.0
Air circulation (Hi / Me / Lo)
CFM
424 / 318 / 283
Moisture removal (High)
Pints / h
5.3
–
ELECTRICAL RATINGS
Voltage rating
V
208
230
208
230
Available voltage range
V
187 - 253
187 - 253
Running amperes
A
0.58
0.60
0.53
0.55
Power input
W
116
134
106
122
Power factor
%
96
97
96
96
Max. starting amperes
A
1
1
1
1
FEATURES
Controls
Microprocessor
Timer
ON / OFF Timer (Max. 72 hr)
Fan speeds
3 and Automatic control
Air fi lter
Washable, easy access
Refrigerant control
Electronic expansion valve
Operation sound (Hi / Me / Lo)
dB-A
38 / 35 / 31
Refrigerant tubing connections
Flare type
Refrigerant tube
diameter
Liquid tube
in. (mm)
1 / 4 (6.35)
Gas tube
in. (mm)
1 / 2 (12.7)
Drain connection
OD 1-1/4"
Remote controller
Optional (Wired / Wireless)
Refrigerant tubing kit / Accessories
Optional / –
Color (Approximate value)
Munsell 10Y 9.3 / 0.4, RAL 9010-GL
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height
in. (mm)
24-7 / 32 (615)
27-5 / 16 (694)
Width
in. (mm)
54-11 / 32 (1380)
57-15 / 16 (1472)
Depth
in. (mm)
9-1 / 16 (230)
12-9 / 32 (312)
Net weight
lbs. (kg)
86 (39)
Shipping weight
lbs. (kg)
90 (41)
Shipping volume
ft
3
(m
3
)
3.43 (0.319)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB
Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB
TD831149-00̲3WAY.indb 124
2010/01/26 15:11:26
FORM 121.00-EG1
ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
128
Floor Exposed (JF Type)
Summary of Contents for JA Series
Page 181: ...Schematic Diagram JDHX3652N FORM 121 00 EG1 ISSUE DATE 5 31 2012 181 JOHNSON CONTROLS ...
Page 183: ...Schematic Diagram JDHX4852N FORM 121 00 EG1 ISSUE DATE 5 31 2012 183 JOHNSON CONTROLS ...
Page 189: ...Schematic Diagram JKHX1862N FORM 121 00 EG1 ISSUE DATE 5 31 2012 189 JOHNSON CONTROLS ...
Page 191: ...Schematic Diagram JKHX2452N FORM 121 00 EG1 ISSUE DATE 5 31 2012 191 JOHNSON CONTROLS ...