![Johnson Controls JA Series Engineering Manual Download Page 69](http://html.mh-extra.com/html/johnson-controls/ja-series/ja-series_engineering-manual_2023361069.webp)
1
2
3
4
5
6
7
8
MODEL No.
Indoor Unit
J
UMHX1562
N
POWER SOURCE
208 - 230 V / 1ø / 60 Hz
PERFORMANCE
Cooling
Heating
Capacity
BTU / h
15,000
17,000
kW
4.5
5.0
Air circulation (Hi / Me / Lo)
CFM
371 / 336 / 283
Moisture removal (High)
Pints / h
3.6
–
External static pressure (High)
in. WG
0.06 : At shipment 0.16 : Using short circuit connection
ELECTRICAL RATINGS
Voltage rating
V
208
230
208
230
Available voltage range
V
187 - 253
187 - 253
Running amperes
A
0.34
0.33
0.36
0.35
Power input
W
44
46
47
49
Power factor
%
62
61
63
61
Max. starting amperes
A
–
–
–
–
FEATURES
Controls
Microprocessor
Timer
ON / OFF Timer (Max. 72 hr)
Fan speeds
3 and Automatic control
Air fi lter
Washable
Refrigerant control
Electronic expansion valve
Operation sound (Hi / Me / Lo)
dB-A
34 / 32 / 30
Using short circuit connection (Hi / Me / Lo)
dB-A
36 / 34 / 32
Refrigerant tubing connections
Flare type
Refrigerant tube
diameter
Liquid tube
in. (mm)
1 / 4 (6.35)
Gas tube
in. (mm)
1 / 2 (12.7)
Drain connection
OD 1-1/4”
Drain pump
Max. head 1.6 ft. above drain connection
Remote controller
Optional (
J
RCS-TM80BG
N
,
J
RCS-BH80AABWL
N
)
Refrigerant tubing kit / Accessories
– / Short Circuit Connection
Color (Approximate value)
–
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height
in. (mm)
7-7 / 8 (200)
8-21 / 32 (220)
Width
in. (mm)
29-17 / 32 (750)
40-35 / 64 (1030)
Depth
in. (mm)
25-13 / 64 (640)
29-21 / 64 (745)
Net weight
lbs. (kg)
42 (19)
Shipping weight
lbs. (kg)
51 (23)
Shipping volume
ft
3
(m
3
)
5.97 (0.169)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 80°F DB / 67°F WB; Outdoor air temperature 95°F DB
Heating: Indoor air temperature 70°F DB; Outdoor air temperature 47°F DB / 43°F WB
TD831149-00̲3WAY.indb 59
2010/01/26 15:11:12
FORM 121.00-EG1
ISSUE DATE: 5/31/2012
69
JOHNSON CONTROLS
Slim Concealed Duct, Standard and Slim (JU, JUM Type)
Unit specifications (M)
Summary of Contents for JA Series
Page 181: ...Schematic Diagram JDHX3652N FORM 121 00 EG1 ISSUE DATE 5 31 2012 181 JOHNSON CONTROLS ...
Page 183: ...Schematic Diagram JDHX4852N FORM 121 00 EG1 ISSUE DATE 5 31 2012 183 JOHNSON CONTROLS ...
Page 189: ...Schematic Diagram JKHX1862N FORM 121 00 EG1 ISSUE DATE 5 31 2012 189 JOHNSON CONTROLS ...
Page 191: ...Schematic Diagram JKHX2452N FORM 121 00 EG1 ISSUE DATE 5 31 2012 191 JOHNSON CONTROLS ...