8
7
6
5
4
3
2
MODEL No.
J
UMHX1862
N
Power source
208 - 230 V / 1 ø / 60Hz
Controller P.C.B. Ass'y
CR-UMHX0762 (Microprocessor)
Fan...(Number diameter / length in. (mm))
Centrifugal (2...ø5-45/64 (ø145))
Fan motor
Model...Nominal output
W
DK8-63G280HB...50 W
Power source
280 / 340 VDC / 3 phase / 60 Hz
No. of pole...r.p.m. (230V, High)
rpm
8P... 1,191
Coil resistance
(Ambient temperature 20°C)
–
Run capacitor
VAC, μF
–
Electronic expansion valve
Coil
UKV-U032E
Coil resistance (at 20°C)
ORG – GRY : 46
YEL – GRY : 46
RED – GRY : 46
BLK – GRY : 46
Valve body
UKV-25D32
Heat exchanger
Coil
Aluminium plate fin / Copper tube
Rows...fi n pitch
in. (mm)
3...1/16 (1.4)
Face area
ft
2
(m
2
)
1.2 (0.111)
Drain pump
ZPLD-12230ST-XH-B
Rated
V, Hz, W
AC 230 V, 60 Hz, 10.8 W
Total head & capacity
(above drain connection)
ft. (mm), gal/
min (cc/min)
1.6 (500), 0.11 (400)
TD831149-00̲3WAY.indb 74
2010/01/26 15:11:14
FORM 121.00-EG1
ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
84
Slim Concealed Duct, Standard and Slim (JU, JUM Type)
Indoor unit (N)
Summary of Contents for JA Series
Page 181: ...Schematic Diagram JDHX3652N FORM 121 00 EG1 ISSUE DATE 5 31 2012 181 JOHNSON CONTROLS ...
Page 183: ...Schematic Diagram JDHX4852N FORM 121 00 EG1 ISSUE DATE 5 31 2012 183 JOHNSON CONTROLS ...
Page 189: ...Schematic Diagram JKHX1862N FORM 121 00 EG1 ISSUE DATE 5 31 2012 189 JOHNSON CONTROLS ...
Page 191: ...Schematic Diagram JKHX2452N FORM 121 00 EG1 ISSUE DATE 5 31 2012 191 JOHNSON CONTROLS ...