8
7
6
5
4
3
2
MODEL No.
Indoor Unit
J
XMHX185
2N
SOURCE
208 - 230 V / 1ø / 60 Hz
PERFORMANCE
Cooling
Heating
Capacity
BTU / h
19,000
21,000
kW
5.6
6.3
Air circulation (Hi / Me / Lo)
CFM
440 / 370 / 320
Moisture removal (High)
Pints / h
4.0
–
ELECTRICAL RATINGS
Voltage rating
V
208
230
208
230
Available voltage range
V
187 - 253
187 - 253
Running amperes
A
0.32
0.30
0.30
0.27
Power input
W
52
56
48
47
Power factor
%
78
81
77
76
Max. starting amperes
A
1
1
1
1
FEATURES
Controls
Microprocessor
Timer
ON / OFF Timer (Max. 72 hr)
Fan speeds
3 and Automatic control
Air filter
Washable, easy access, long life (2,500 hr)
Refrigerant control
Electronic expansion valve
Operation sound (Hi / Me / Lo)
dB-A
41 / 37 / 33
Refrigerant tubing connections
Flare type
Refrigerant tube di-
ameter
Liquid tube
in. (mm)
1 / 4 (6.35)
Gas tube
in. (mm)
1 / 2 (12.7)
Drain connection
OD 1-1/4"
Drain pump
Max. head 2.1 ft. above drain connection
Panel
Optional (
J
PNR-XMH1852
N
)
Remote controller
Optional (
J
RCS-TM80BG
N
,
J
RCS-XM18AABWL
N
)
Refrigerant tubing kit / Accessories
Optional / –
Color (Approximate value)
Munsell 2.5GY 9.0 / 0.5, RAL 9001-GL (resemblant color)
DIMENSIONS & WEIGHT
Indoor unit (including panel)
Package
Body
Panel
Unit dimensions
Height
in. (mm)
12-3 / 8 (313)
11-3 / 8 (290)
4-1 / 8 (105)
Width
in. (mm)
24-5 / 8 (625)
28-1 / 8 (714)
26-1 / 4 (665)
Depth
in. (mm)
24-5 / 8 (625)
24-3 / 4 (630)
26-5 / 8 (678)
Net weight
lbs. (kg)
40.6 (18.4)
–
–
Shipping weight
lbs. (kg)
–
41.9 (19)
7.7 (3.5)
Shipping volume
ft
3
(m
3
)
–
4.6 (0.13)
1.7 (0.047)
Rated conditions
Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
TD831149-00̲3WAY.indb 22
2010/01/26 15:11:04
FORM 121.00-EG1
ISSUE DATE: 5/31/2012
JOHNSON CONTROLS
32
4-Way Air Discharge Ceiling Semi-Concealed, Standard and Mini (JX, JXM Types)
Unit specifications (F)
Summary of Contents for JA Series
Page 181: ...Schematic Diagram JDHX3652N FORM 121 00 EG1 ISSUE DATE 5 31 2012 181 JOHNSON CONTROLS ...
Page 183: ...Schematic Diagram JDHX4852N FORM 121 00 EG1 ISSUE DATE 5 31 2012 183 JOHNSON CONTROLS ...
Page 189: ...Schematic Diagram JKHX1862N FORM 121 00 EG1 ISSUE DATE 5 31 2012 189 JOHNSON CONTROLS ...
Page 191: ...Schematic Diagram JKHX2452N FORM 121 00 EG1 ISSUE DATE 5 31 2012 191 JOHNSON CONTROLS ...