1
2
3
4
5
6
7
8
3. 1-Way Air Discharge Semi-concealed Type (A Type)
Unit specifi cations (B)
MODEL No.
Indoor Unit
J
AHX095
2N
POWER SOURCE
208 - 230 V / 1ø / 60 Hz
PERFORMANCE
Cooling
Heating
Capacity
BTU / h
9,600
11,000
kW
2.8
3.2
Air circulation (Hi / Me / Lo)
CFM
280 / 250 / 210
Moisture removal (High)
Pints / h
2.75
–
ELECTRICAL RATINGS
Voltage rating
V
208
230
208
230
Available voltage range
V
187 - 253
187 - 253
Running amperes
A
0.29
0.28
0.28
0.26
Power input
W
48
50
44
46
Power factor
%
80
78
76
77
Max. starting amperes
A
1
1
1
1
FEATURES
Controls
Microprocessor
Fan speeds
3 and Automatic control
Airflow direction
Automatic (Remote control)
Air filter
Washable, easy access, long life
Refrigerant control
Electronic expansion valve
Operation sound (Hi / Me / Lo)
dB-A
33 / 31 / 29
Refrigerant tubing connections
Flare type
Refrigerant tube di-
ameter
Liquid tube
in. (mm)
1 / 4 (6.35)
Gas tube
in. (mm)
1 / 2 (12.7)
Drain connection
25 A, OD 1-1/4"
Drain pump
Max. head 2.1 ft. above drain connection
Panel
Optional (
J
PNR-AH1252
N
)
Remote controller
Optional (
J
RCS-TM80BG
N
,
J
RCS-TRP80ABWL
N
)
Refrigerant tubing kit / Accessories
Optional / –
Color (Approximate value)
Munsell 2.5GY 9.0 / 0.5, RAL 9001-GL (resemblant color)
DIMENSIONS & WEIGHT
Indoor unit (including panel)
Package
Body
Panel
Unit dimensions
Height
in. (mm)
13 (330)
14-3 / 16 (360)
4-13 / 32 (112)
Width
in. (mm)
29-29 / 32 (760)
31-3 / 32 (790)
31-1 / 2 (800)
Depth
in. (mm)
24-3 / 8 (620)
23-15 / 32 (596)
27-9 / 16 (700)
Net weight
lbs. (kg)
43 (19.5)
–
–
Shipping weight
lbs. (kg)
–
60 (27)
9 (4.0)
Shipping volume
ft
3
(m
3
)
–
6.0 (0.170)
2.2 (0.062)
Rated conditions
Cooling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
TD831149-00̲3WAY.indb 39
2010/01/26 15:11:07
FORM 121.00-EG1
ISSUE DATE: 5/31/2012
49
JOHNSON CONTROLS
1-Way Air Discharge Ceiling Semi-Concealed (JA Type)
Summary of Contents for JA Series
Page 181: ...Schematic Diagram JDHX3652N FORM 121 00 EG1 ISSUE DATE 5 31 2012 181 JOHNSON CONTROLS ...
Page 183: ...Schematic Diagram JDHX4852N FORM 121 00 EG1 ISSUE DATE 5 31 2012 183 JOHNSON CONTROLS ...
Page 189: ...Schematic Diagram JKHX1862N FORM 121 00 EG1 ISSUE DATE 5 31 2012 189 JOHNSON CONTROLS ...
Page 191: ...Schematic Diagram JKHX2452N FORM 121 00 EG1 ISSUE DATE 5 31 2012 191 JOHNSON CONTROLS ...