![Johnson Controls Frick RXB Plus 12 Installation Operation & Maintenance Download Page 20](http://html.mh-extra.com/html/johnson-controls/frick-rxb-plus-12/frick-rxb-plus-12_installation-operation-and-maintenance_2023231020.webp)
RXB PLUS ROTARY SCREW COMPRESSOR UNITS
OPERATION
070.101-IOM (JAN 13)
Page 20
Compressor Differential Cutout -
The.differential.cutout.
has.been.lowered.from.55.lb.to.25.lb..Cutout.will.occur.after.
five.minutes...To.allow.operation.at.low.differential.pressures,.
the.micro.will.take.the.following.steps:
A.
.Force.unload.the.compressor.to.50%.and.display.an.“F.
Unload”.when.the.oil.pressure.is.within.10.lb.of.the.main.oil.
injection.port.pressure.and.the.slide.valve.position.is.greater.
than.50%.
B.
Prohibit.the.compressor.from.loading.and.display.a.“Ld.
Inhib”.message.when.the.differential.is.within.15.lb.of.the.
main.oil.injection.port.pressure.
Oil Pressure Alarm and cutout -
Prelube.and.Cycling.Oil.
Pump.version.when.pump.is.not.running...Alarm.will.occur.if.
oil.pressure.is.25.lb.below.discharge.pressure.or.within.10.
lb.of.suction.pressure.for.30.seconds...Cutout.occurs.if.oil.
pressure.is.30.lb.below.discharge.pressure.or.if.oil.pressure.
is.within.7.lb.of.suction.pressure.for.10.seconds.and.alarm.
has.already.been.set.
Full.Lube.and.Cycling.Oil.Pump.version.when.oil.pump.is.run-
ning...Alarm.occurs.if.oil.pressure.is.within.10.lb.of.discharge.
pressure.for.30.seconds...Cutout.occurs.when.oil.pressure.
is.within.5.lb.of.discharge.pressure.for.10.seconds.and.oil.
pressure.alarm.has.been.set.
Cycling Oil Pump Control -
The.oil.pump.will.cut.off.when.
differential.pressure.between.suction.and.discharge.pressure.
is.55.lb.or.greater...Upon.pump.termination.the.above.cutout.
logic.(pump.not.running).is.utilized...Pump.cut-in.occurs.when.
the.differential.pressure.between.suction.and.discharge.is.
45.lb.or.less...Oil.pressure.alarm.and.cutout.logic.(pump.
running).begins.after.a.30.second.delay.which.allows.the.oil.
pump.to.build.pressure.
Prealarms.are.self-clear.ing..At.this.time.the.alarm.will.stop.
flashing,.but.the.time.of.the.first.occur.rence.will.still.be.re-
corded.to.the.right.of.the.alarm..Pressing.the.
[CLEAR]
.key.
while.at.the.Annunciator.display.will.clear.all.alarms.and/or.
cutouts.
In. order. to. restore. the. Annunciator. display. and. resume.
normal.operation.it.will.be.necessary.to.go.through.the.fol-
lowing.steps:
1.
.Correct.the.conditions.causing.the.alarm.
2.
.Press.the.
[ALARM SILENCE]
.key..(This.action.may..pre-
cede.correcting.the.conditions.causing.the.alarm).
3.
. To. clear. or. reset. the. Annunciator. pages,. press. the.
[CLEAR]
.key..This.will.also.clear.the.ALARM.or.CUTOUT.
indicator.from.the.Operat.ing.display.
4.
.Press.
[F1]
.to.call.up.the.Operating.dis.play..If.the.condi-
tions.causing.the.alarm.have.not.been.cor.rect.ed.or.a.new.
fault. has. occurred,. a. new.
ALARM
. or.
CUTOUT
. message.
will.appear.
NOTE: Use of the Emergency Stop Button may trip one
or more alarm setpoints.
SHUTDOWN RECORD DISPLAY *
. SHUTDOWN.RECORD.P1.Thu.03-01-89.15:33:36..
. Hi.Oil.Temp.Cutout. *********************..
. Hi.Oil.Temp.Cutout. *********************..
. Low....Temp.Cutout. *********************..
..*Display.for.illustrative.purposes.only.
. SHUTDOWN.RECORD.P2.Thu.03-01-89.15:33:36
.. Low....Temp.Cutout. *********************
. Disch..Temp.Cutout. *********************
. Disch..Temp.Cutout. *********************
The.Shutdown.Record.display.keeps.a.record.of.the.last.six.
shutdowns.(cutouts)..This.information.will.help.troubleshoot.
persistent.operational.problems..The.most.recent.cutout.will.
appear.on.the.top.line.of.page.1.of.the.display.with.the.old-
est.ap.pearing.on.the.last.or.bottom.line.of.page.2..When.a.
cutout.occurs,.all.information.is.moved.down.one.line.and.the.
new.cutout.appears.at.the.top.of.page.1..When.the.dis.play.
is.full,.the.oldest.record.is.dropped.off.the.display.and.is.not.
retained. in. memory..The. informa.tion. presented. is. echoed.
from.the.Annun.ciator.display,.providing.the.type.of.cutout,.
the.day,.the.date,.and.the.time..
NOTE: This informa tion
will not be lost due to power failure.
FREEZE DISPLAY *
. FREEZE.DISPLAY.P1..Thu.03-01-89.15:33:36
. Suction. Disch. Oil. CUTOUT. Compressor
. 14.3.hg. 120.g. 060.g.
.
OFF..Mode
.
-040.F.
135.F. 135.F
. FREEZE.DISPLAY.P2..Thu.03-01-89.15:33:36
. V.Ratio. SV.Pos.
Pump.
%FLA. Sep.132
O
F
.
2.2.
000%.
off.
000%.
HTR.off
.
Auto.
Auto.L
The.Freeze.display.has.the.same.appearance.and.con.tains.
the.same.information.as.the.Oper.ating.display..(For.a.descrip-
tion.of.the.informa.tion.presented.by.the.Freeze.display,.refer.
to. the. Operating. display.).The. Freeze. display. freezes. the.
information.of.the.Operating.display.
AT THE MOMENT OF
A COMPRESSOR CUTOUT
..The.information.on.the.Freeze.
display.can.help.the.operator.to.identify.the.cause.of.a.fault.
which.occurred.when.no.one.was.present..The.Freeze.display.
will.retain.the.information.generated.by.a.cutout.until.a.new.
cutout.occurs.or.power.is.removed.from.the.micro.processor.
Do not confuse the Freeze display
with the Operating display. In order
to avoid confusion remember that
the displayed informa tion on the Operating display is
constantly being updated and changed. The Freeze
display is fixed and FREEZE DISPLAY appears in the
upper left hand corner of the display.
NOTE: The Freeze display will appear as a blank screen
when power is initially furnished to the unit, and it will
return to a blank screen anytime power is removed from
the micropro cessor.
SECURITY DISPLAY *
. SECURITY.DISPLAY.
Press.F2.To.Exit
. Setpoints.Access.---- [Enabled.].Keyboard....
. Enter.Access.Code.-- [*****]
.The.
[F2]
.function.key.will.call.up.the.Security.display..The.
Security.display.allows.the.operator.to.either.enable.or.dis-
able. the. microprocessor’s. keyboard. and,. thereby,. prevent.