
Due to continuous improvement, TRIATEK reserves the right to change product specifications without notice.
-
1
-
Due to continuous improvement, JCI reserves the right to change product specifications without notice.
Electrical
Optional External Remote Sensor Distance……………………………………………………………………………………………………Up to 1,000 feet
Optional External Remote Sensor....………………………………………………………………………………Wiring 18-22 AWG, shielded twisted pair
Power Supply..…………………………………………………………………………………………………………………………………24 Vac ±10%, 30Va
Accuracy of Measurement.....……………………………………………………………………………………………………………………………±0.5%FS
Pressure Range
(NIST Traceable / Individual certification available as option)
…………………………………………………………………±0.2500 “WC
Pressure/Flow……………………………………………………………………………………………………………………………………up to 0.25 ”WC
4 Analog Inputs…………………………………………………………………………………………………………………4-20mAdc, 0-5Vdc or 0-10Vdc
4 Analog Outputs………………………………………………………………………………………………………………4-20mAdc, 0-5Vdc or 0-10Vdc
2 Thermistor Inputs…………………………………………………………………………………………………………NTC Type 2 or 3, 10kΩ @ 25°C
4 Digital Inputs………………………………………………………………………………………………0-5Vdc or 0-24Vdc, Active-High or Active-Low
3 Relay Outputs...………………………………………………………………………………………………………………………………………1A@24Vdc
Control Signal Wire Size............……………………………………………………………………………………………………………………18-22 AWG
Power Supply………………………Class 2, 24Vac ±10%, 30VA universal 120/240 to 24 Vac, 60/50 Hz, step-down isolation transformer provided
Communications
BACnet® MS/TP network....…………………………………………………………………………………………Two-Wire Twisted Pair, RS-485 signaling
Metasys
N2 network...………………………………………………………………………………………………Two-Wire Twisted Pair, RS-485 signaling
Recommended Cable Type...……………………………………………………………………………………………………………………… Belden 3107A
Touchscreen User Interface
LCD Size....……………………………………………………………………………………………………………………………………………3.2” diagonal
LCD Type.....……………………………………………………………………………………………………………………………………………Transmissive
Resolution...………………………………………………………………………………………………………………………………………240 x 320 portrait
Viewing Area..……………………………………………………………………………………………………………………………50.60 mm x 66.80 mm
Color Depth.…………………………………………………………………………………………………………………………………18-bit or 262K colors
Backlight Color.....………………………………………………………………………………………………………………………………………………White
Luminous Intensity...………………………………………………………………………………………………………………………………Min 2500 cd/m2
Recommended Cable Type (applicable to surface mount models FMS-1655-s-x only)…………………………………………………… Belden 3125A
Mechanical
FMS-1655 Internal Sensor Flush Mount Housing (Brushed Stainless Steel) Housing..……………………………………………5.6”W x 8.5”H x 1.9”D
FMS-1655 Display Module Housing………………………………………………………………………………………………………3”W x 5”H x 1.13”D
Stainless Steel Cover Plate for Flow Tube……………………………………………………………………………………………2.7”W x 4.5”H x 0.2”D
Stainless Steel Cover Plate for Remote Sensor………………………………………………………………………………………2.7”W x 4.5”H x 0.2”D
FMS-1655 with Flow Tube Cover Plate……………………………………………………………………………………………………………approx. 3.5 lb
FMS-1655 with Optional External Remote Sensor………………………………………………………………………………………………approx. 4.0 lb
FMS-1655 Mounting Options...……………………………………………………………………………………………………………………Surface, Flush
Flow Tube Cover Plate Mounting..……………………………………………………………………………………………………………………………Flush
Environmental
Operating Temperature..…………………………………………………………………………………………………………………32° to 125° F Operating
Operating Humidity……………………………………………………………………………………………………………10% - 95% RH, Non-condensing
GENERAL
Specifications
Summary of Contents for FMS-1655 Series
Page 2: ...Notes ...
Page 34: ...SUBHEAD 27 MOUNTING WIRING Notes ...
Page 40: ...SUBHEAD 33 MOUNTING WIRING Power Step Down Isolation Transformer provided with FMS Controller ...
Page 42: ...SUBHEAD 35 MOUNTING WIRING Notes ...
Page 57: ... 50 Notes ...
Page 60: ...Integrated Flush Mount Wiring Box Dimensions 53 ...
Page 61: ...Flush Mount Bracket Dimensions 54 ...
Page 62: ...Thin Mount Wiring Box Dimensions 55 ...