Table 1. Analog Input Configuration Settings (S1)
Mode
S1 - 1
S1 - 2
S1 - 3
S1 - 4
S1 - 5
S1 - 6
S1 - 7
S1 - 8
AI-1 5Vdc
OFF
OFF
AI-1 20mA
ON
OFF
AI-1 10Vdc
OFF
ON
Not Valid
ON
ON
AI-2 5Vdc
OFF
OFF
AI-2 20mA
ON
OFF
AI-2 10Vdc
OFF
ON
Not Valid
ON
ON
AI-3 5Vdc
OFF
OFF
AI-3 20mA
ON
OFF
AI-3 10Vdc
OFF
ON
Not Valid
ON
ON
AI-4 5Vdc
OFF
OFF
AI-4 20mA
ON
OFF
AI-4 10Vdc
OFF
ON
Not Valid
ON
ON
SUBHEAD
Configurations & Settings
-
45
-
MODULE SETTINGS
Table 2. Protocol Selection Settings (S3)
Protocol Selection
S3-7
S3-8
Reserved
OFF
OFF
Metasys® N2
ON
OFF
BACnet® MS/TP (default)
ON
ON
Controller Configuration Dipswitch (S4)
1.
AO-1 Voltage Range Selection:
OFF = 0-10Vdc
ON = 0 - 5Vdc
2.
AO-2 Voltage Range Selection:
OFF = 0-10Vdc
ON = 0 - 5Vdc
3.
AO-3 Voltage Range Selection:
OFF = 0-10Vdc
ON = 0 - 5 Vdc
4.
AO-4 Voltage Range Selection:
OFF = 0-10Vdc
ON = 0 - 5 Vdc
Controller Configuration Slideswitch (S5):
LEFT = Digital Inputs pulled-high (triggered by active low input - default)
RIGHT = Digital Inputs pulled-low (triggered by active high input, up to 24Vdc)
Summary of Contents for FMS-1655 Series
Page 2: ...Notes ...
Page 34: ...SUBHEAD 27 MOUNTING WIRING Notes ...
Page 40: ...SUBHEAD 33 MOUNTING WIRING Power Step Down Isolation Transformer provided with FMS Controller ...
Page 42: ...SUBHEAD 35 MOUNTING WIRING Notes ...
Page 57: ... 50 Notes ...
Page 60: ...Integrated Flush Mount Wiring Box Dimensions 53 ...
Page 61: ...Flush Mount Bracket Dimensions 54 ...
Page 62: ...Thin Mount Wiring Box Dimensions 55 ...