BACnet
®
OBJECTS
BACnet
®
Objects
-
46
-
The following table itemizes the list of points available for integration in a building management system (BMS). This table contains the objects
for open BACnet integration.
Object
Read
Analog Inputs
AI - 1
Analog Input 1 (default: Isolation Pressure)
Read-Only
AI - 2
Analog Input 2
Read-Only
AI - 3
Analog Input 3
Read-Only
AI - 4
Analog Input 4
Read-Only
AI - 5
Thermistor Input 1
Read-Only
AI - 6
Thermistor Input 2
Read-Only
Analog Outputs
AO - 1
Analog Output 1 (default: Damper Position)
Read-Only
AO - 2
Analog Output 2 (default: Anteroom Damper Control)
Read-Only
AO - 3
Analog Output 3 (spare control output)
Read-Only
AO - 4
Analog Output 4 (spare control output)
Read-Only
Binary Inputs
BI - 1
Digital Input 1 (default: Door Switch)
Read-Only
BI - 2
Digital Input 2 (default: Anteroom Door Switch)
Read-Only
BI - 3
Digital Input 3 (spare digital input)
Read-Only
BI - 4
Digital Input 4 (spare digital input)
Read-Only
Binary Outputs
BO - 1
Relay Output 1 (default: Primary Alarm Relay Output)
Read-Only
BO - 2
Relay Output 2 (default: Spare Relay Output)
Read-Only
BO - 3
Relay Output 3 (spare relay output)
Read-Only
BO - 4
Not user-selectable
Read-Only
Analog Values
AV - 1
AI-1 Setpoint (Room Pressure)
Read/Write
AV - 2
AI-2 Setpoint
Read/Write
AV - 3
AI-3 Setpoint
Read/Write
AV - 4
AI-4 Setpoint
Read/Write
Analog Values (continued)
AV - 5
TI-1 Setpoint
Read/Write
AV - 6
TI-2 Setpoint
Read/Write
AV - 7
Air Change Rate based on Flow Input at AI-1
Read/Write
AV - 8
Air Change Rate based on Flow Input at AI-2
Read/Write
AV - 9
Air Change Rate based on Flow Input at AI-3
Read/Write
AV - 10
Air Change Rate based on Flow Input at AI-4
Read/Write
AV - 11
Alarm Relay 1 High Setpoint
Read/Write
AV - 12
Alarm Relay 1 Low Setpoint
Read/Write
AV - 13
Alarm Relay 2 High Setpoint
Read/Write
AV - 14
Alarm Relay 2 Low Setpoint
Read/Write
AV - 15
Alarm Relay 3 High Setpoint
Read/Write
AV - 16
Alarm Relay 3 Low Setpoint
Read/Write
AV - 17
Not user-selectable
Read/Write
AV - 18
Not user-selectable
Read/Write
AV - 19
AI-1 Low Alarm Setpoint (low pressure alarm)
Read/Write
AV - 20
AI-1 Low Warning Setpoint (low pressure warning)
Read/Write
AV - 21
AI-1 High Warning Setpoint (high pressure warning)
Read/Write
AV - 22
AI-1 High Alarm Setpoint (high pressure alarm)
Read/Write
AV - 23
AI-2 Low Alarm Setpoint
Read/Write
AV - 24
AI-2 Low Warning Setpoint
Read/Write
AV - 25
AI-2 High Warning Setpoint
Read/Write
AV - 26
AI-2 High Alarm Setpoint
Read/Write
AV - 27
AI-3 Low Alarm Setpoint
Read/Write
AV - 28
AI-3 Low Warning Setpoint
Read/Write
AV - 29
AI-3 High Warning Setpoint
Read/Write
AV - 30
AI-3 High Alarm Setpoint
Read/Write
AV - 31
AI-4 Low Alarm Setpoint
Read/Write
Summary of Contents for FMS-1655 Series
Page 2: ...Notes ...
Page 34: ...SUBHEAD 27 MOUNTING WIRING Notes ...
Page 40: ...SUBHEAD 33 MOUNTING WIRING Power Step Down Isolation Transformer provided with FMS Controller ...
Page 42: ...SUBHEAD 35 MOUNTING WIRING Notes ...
Page 57: ... 50 Notes ...
Page 60: ...Integrated Flush Mount Wiring Box Dimensions 53 ...
Page 61: ...Flush Mount Bracket Dimensions 54 ...
Page 62: ...Thin Mount Wiring Box Dimensions 55 ...