Analog Input Configuration Dipswitch (S1)
1.
AI-1 Mode Selection:
OFF = voltage input
ON = current input
2.
AI-2 Mode Selection:
OFF = voltage input
ON = current input
3.
AI-3 Mode Selection:
OFF = voltage input
ON = current input
4.
AI-4 Mode Selection:
OFF = voltage input
ON = current input
5.
AI-1 Voltage Range Selection:
OFF = 0-5Vdc
ON = 0-10Vdc
6.
AI-2 Voltage Range Selection:
OFF = 0-5Vdc
ON = 0-10Vdc
7.
AI-3 Voltage Range Selection:
OFF = 0-5Vdc
ON = 0-10Vdc
8.
AI-4 Voltage Range Selection:
OFF = 0-5Vdc
ON = 0-10Vdc
NOTES: To configure FMS-1655 for an internal sensor, set dipswitch position 1 to OFF and dipswitch position 5 to OFF. To configure
FMS-1655 for a remote sensor, set dipswitch position 1 to ON and dipswitch position 5 to OFF. For other inputs, see Table 1.
Analog Output Configuration Dipswitch (S3)
1.
AO-1 Mode Selection:
OFF = current output
ON = voltage output
2.
AO-2 Mode Selection:
OFF = current output
ON = voltage output
3.
AO-3 Mode Selection:
OFF = current output
ON = voltage output
4.
AO-4 Mode Selection:
OFF = current output
ON = voltage output
Network Configuration Dipswitch (S3)
5.
RS485 Network Termination:
OFF = disabled
ON = enabled
6.
RS485 Display Termination:
OFF = disabled
ON = enabled
7.
Protocol Select: see Table 2 below
8.
Protocol Select: see Table 2 below
MODULE SETTINGS
-
44
-
Configuring Main Controller Module Settings
Summary of Contents for FMS-1655 Series
Page 2: ...Notes ...
Page 34: ...SUBHEAD 27 MOUNTING WIRING Notes ...
Page 40: ...SUBHEAD 33 MOUNTING WIRING Power Step Down Isolation Transformer provided with FMS Controller ...
Page 42: ...SUBHEAD 35 MOUNTING WIRING Notes ...
Page 57: ... 50 Notes ...
Page 60: ...Integrated Flush Mount Wiring Box Dimensions 53 ...
Page 61: ...Flush Mount Bracket Dimensions 54 ...
Page 62: ...Thin Mount Wiring Box Dimensions 55 ...