11
-
MOUNTING/WIRING
FMS-1655 with Standard Remote Sensor (9-Pin)
NC NC GND NC NC Io NC GND +Vi
n
NC NC GND NC NC Io NC GND +Vi
n
~~
~ ~
Standard Remote Sensor Detail
(Bottom View)
ISOLATION
ROOM
CORRIDOR
Stainless Steel
Mounting Plate
Gasket
Louvered Cover
Plate
Stainless Steel
Flow Tube
Mounting Plate
Gasket
Thin Silicone Caulking
(apply around tube and
between stainless steel
plate and wall to seal unit
penetration)
Terminal
For connection of
transmitter to
FMS-1655 .
Flow Tube
When Flow Tube mounting plate is located
directly opposite the sensor, flow tubing must
be cut as short as possible to prevent kinks.
To FMS-1655
Controller
Wall Section
(cutaway view)
Rotating clamps secure
assembly to wall board
Sensor installation requires the use of a three
conductor wire between the sensor and the main
controller module.