SUBHEAD
-
47
-
BACnet
®
OBJECTS
JCI reserves the right to change product specifications without notice.
BACnet
®
Objects
Object
Read
Analog Values (continued)
AV - 32
AI-4 Low Warning Setpoint
Read/Write
AV - 33
AI-4 High Warning Setpoint
Read/Write
AV - 34
AI-4 High Alarm Setpoint
Read/Write
AV - 35
TI-1 Low Alarm Setpoint
Read/Write
AV - 36
TI-1 Low Warning Setpoint
Read/Write
AV - 37
TI-1 High Warning Setpoint
Read/Write
AV - 38
TI-1 High Alarm Setpoint
Read/Write
AV - 39
TI-2 Low Alarm Setpoint
Read/Write
AV - 40
TI-2 Low Warning Setpoint
Read/Write
AV - 41
TI-2 High Warning Setpoint
Read/Write
AV - 42
TI-2 High Alarm Setpoint
Read/Write
AV - 43
Writable Network Variable – Humidity
Read/Write
AV - 44
Writable Network Variable – Temperature
Read/Write
AV - 45
Writable Network Variable – Air Changes
Read/Write
AV - 46
Writable Network Variable – Differential Pressure
Read/Write
AV - 47
Device ID Offset (range: 0 – 4,194,000)
Read/Write
AV - 48
Duct Air Flow based on AI-1 flow input
Read-Only
AV - 49
Duct Air Flow based on AI-2 flow input
Read-Only
AV - 50
Duct Air Flow based on AI-3 flow input (Supply Flow)
Read-Only
AV - 51
Duct Air Flow based on AI-4 flow input (Exhaust Flow)
Read-Only
AV - 52
Volumetric Offset (Supply Flow – Exhaust Flow)
Read-Only
AV - 53
Volumetric Offset Setpoint
Read-Write
AV - 54
AO-1 Override Level
Read-Write
AV - 55
AO-2 Override Level
Read-Write
AV - 56
AO-3 Override Level
Read-Write
AV - 57
AO-4 Override Level
Read-Write
AV - 58
AI-1 Deadband Setting
Read/Write
AV - 59
AI-2 Deadband Setting
Read/Write
Analog Values (continued)
AV - 60
AI-3 Deadband Setting
Read/Write
AV - 61
AI-4 Deadband Setting
Read/Write
AV - 62
TI-1 Deadband Setting
Read/Write
AV - 63
TI-2 Deadband Setting
Read/Write
Multistate Objects
MSO - 1
Primary solation Mode: 1=positive, 2=negative, 3=neutral
Read/Write
MSO - 2
Secondary Isolation Mode: 1=positive, 2=negative, 3=neutral
Read/Write
MSO - 3
Primary Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only
MSO - 4
Secondary Alarm Status: 1=normal, 2=warning, 3=alarm Read-Only
MSO - 5
AI-3 Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only
MSO - 6
AI-4 Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only
MSO - 7
TI-1 Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only
MSO - 8
TI-2 Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only
MSO - 9
Offset Control Status
Read-Only
Summary of Contents for FMS-1655 Series
Page 2: ...Notes ...
Page 34: ...SUBHEAD 27 MOUNTING WIRING Notes ...
Page 40: ...SUBHEAD 33 MOUNTING WIRING Power Step Down Isolation Transformer provided with FMS Controller ...
Page 42: ...SUBHEAD 35 MOUNTING WIRING Notes ...
Page 57: ... 50 Notes ...
Page 60: ...Integrated Flush Mount Wiring Box Dimensions 53 ...
Page 61: ...Flush Mount Bracket Dimensions 54 ...
Page 62: ...Thin Mount Wiring Box Dimensions 55 ...