SUBHEAD
-
49
-
METASYS
®
N2 OBJECTS
Metasys
®
N2 Objects
Object
Read
Internal Float Values (continued)
ADF - 35
AI-4 High Alarm Setpoint
Read/Write
ADF - 36
TI-1 Low Alarm Setpoint
Read/Write
ADF - 37
TI-1 Low Warning Setpoint
Read/Write
ADF - 38
TI-1 High Warning Setpoint
Read/Write
ADF - 39
TI-1 High Alarm Setpoint
Read/Write
ADF - 40
TI-2 Low Alarm Setpoint
Read/Write
ADF - 41
TI-2 Low Warning Setpoint
Read/Write
ADF - 42
TI-2 High Warning Setpoint
Read/Write
ADF - 43
TI-2 High Alarm Setpoint
Read/Write
ADF - 44
Humidity Network Variable (writable)
Read/Write
ADF - 45
Temperature Network Variable (writable)
Read/Write
ADF - 46
Air Changes Network Variable (writable)
Read/Write
ADF - 47
Differential Pressure Network Variable (writable)
Read/Write
ADF - 48
Air Flow based on Flow Input at AI-1
Read-Only
ADF - 49
Air Flow based on Flow Input at AI-2
Read-Only
ADF - 50
Air Flow based on Flow Input at AI-3 (default: Supply
Read-Only
ADF - 51
Air Flow based on Flow Input at AI-4 (default: Exhaust
Read-Only
ADF - 52
Volumetric Offset (Supply Flow – Exhaust Flow)
Read-Only
ADF - 53
Volumetric Offset Setpoint
Read-Write
ADF - 54
AO-1 Override Level
Read-Write
ADF - 55
AO-2 Override Level
Read-Write
ADF - 56
AO-3 Override Level
Read-Write
ADF - 57
AO-4 Override Level
Read-Write
ADF - 58
AI-1 Deadband Setting
Read-Write
ADF - 59
AI-2 Deadband Setting
Read-Write
ADF - 60
AI-3 Deadband Setting
Read-Write
ADF - 61
AI-4 Deadband Setting
Read-Write
ADF - 62
TI-1 Deadband Setting
Read-Write
Internal Float Values (continued)
ADF - 63
TI-2 Deadband Setting
Read-Write
Internal Integer Values
ADI - 1
AI-1 Isolation Mode: 1=positive, 2=negative, 3=neutral
Read/Write
ADI - 2
AI-1 Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only
ADI - 7
AI-2 Isolation Mode: 1=positive, 2=negative, 3=neutral
Read/Write
ADI - 8
AI-2 Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only
ADI - 9
AI-3 Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only
ADI - 10
AI-4 Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only
ADI - 11
TI-1 Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only
ADI - 12
TI-2 Alarm Status: 1=normal, 2=warning, 3=alarm
Read-Only
Summary of Contents for FMS-1655 Series
Page 2: ...Notes ...
Page 34: ...SUBHEAD 27 MOUNTING WIRING Notes ...
Page 40: ...SUBHEAD 33 MOUNTING WIRING Power Step Down Isolation Transformer provided with FMS Controller ...
Page 42: ...SUBHEAD 35 MOUNTING WIRING Notes ...
Page 57: ... 50 Notes ...
Page 60: ...Integrated Flush Mount Wiring Box Dimensions 53 ...
Page 61: ...Flush Mount Bracket Dimensions 54 ...
Page 62: ...Thin Mount Wiring Box Dimensions 55 ...