CK721-A Network Controller

Hardware Installation

24-10025-237 Rev. –

 

2

CK721-A System Specifications (All Panels)

System Configuration Example

N

OTE

Each network device must have a unique IP address because the performance of an entire 

network can be compromised if two devices share the same address. 

Figure 1: Example of a Simple CK721-A System Configuration 

CK721-A Encrypted Communications with the Server

When enabled, encrypted network communications between the CK721-A controller and the server 
uses the Advanced Encryption Standard (AES256). 

The CK721-A Encryption is implemented using the Federal Information Processing Standards (FIPS) 
140-2, validated (Certificate #2398), cryptographic module (version 2.0.9) from the Open Source 
Software Institute (

http://www.oss-institute.org

).

CK721-A controller peer-to-peer User Datagram Protocol (UDP) broadcast messages are not 
encrypted. 

Table 2: System Specifications

Item

Specification

Ambient 
Temperature

32 to 122 °F (0 to 50° C)

Humidity

20% to 80% non-condensing

Ventilation

Cabinets require free movement of air over all exposed surfaces

S300-DIN-L

16x20x6.6 in (41x51x17 cm)
Approximate weight: fully loaded 45lb (20 kg)

S300-DIN-S

12x12x6 in (30x30x15 cm)
Approximate weight: fully loaded 24lb (11 kg)

Cabling

Described in 

Wiring CK721-A and Other Modules

 on page 6.

Backup Battery

S300-BAT in S300-DIN-L: minimum one hour sustained operation at full load.
S300-BAT-2.8AH in S300-DIN-S: minimum one and a half hours sustained operation at full 
load.

Input Power

24VDC, Min 20V, Nom 24V, Max 30V

Summary of Contents for CK721-A

Page 1: ...24 10025 237 Revision December 2017 CK721 A Network Controller hardware installation manual...

Page 2: ...erial returns contact the branch if the material was purchased through a Johnson Controls branch or through the Product Sales Operations Team if ordered through the Advanced Order Management System AO...

Page 3: ...nt must be maintained between 13 35 C 55 95 F and relative humidity of 85 5 by the HVAC system Twenty four hour standby power shall be provided for the HVAC system 6 The installer shall incorporate a...

Page 4: ......

Page 5: ...rds and 8 000 off line transactions Note When the number of badges exceeds 120 000 the number of access groups should be limited to 50 000 All CK721 A panels are connected to the server via a 10 100Ba...

Page 6: ...cate 2398 cryptographic module version 2 0 9 from the Open Source Software Institute http www oss institute org CK721 A controller peer to peer User Datagram Protocol UDP broadcast messages are not en...

Page 7: ...g CK721 A to a Terminal Emulator RS232 Serial Null Modem Cable Wiring on page 6 RS232 B KONE serial server elevator or OTIS serial server elevator controller communications port or ThyssenKrupp serial...

Page 8: ...power is not supplied before you remove the lithium battery the realtime clock will be incorrect LEDs POWER ON is steady when power is applied FAULT OFF indicates normal operation ON indicates a gener...

Page 9: ...l and snap on To remove a module pull the white clips two are located at the bottom and one on top of the module then pull the bottom of the module out and lift it up Wiring Between RS485B and the Fie...

Page 10: ...Listed 22 AWG Stranded Hook up wire Limited to within cabinet Listed 18 AWG 3 cond stranded shielded 4000 ft 1215 m All modules connected to a single CK721 A panel must be within 4000 feet of the pan...

Page 11: ...71 latest edition must be followed for installations in Great Britain Additional information is given in the Cardkey Installers Code of Practice Conduit ground cold water pipes unbrazed joints or diss...

Page 12: ...tant Notes As a security precaution Johnson Controls strongly suggests changing the default controller password during the installation process The CK721 A panel must be set up first using Terminal Em...

Page 13: ...you will be following Serial cable between RS232C A J3 of the CK721 A controller and your laptop or PC serial port or Ethernet cable 2 Start your terminal emulator software 3 For serial communication...

Page 14: ...2000 server Version 3 8 Build 57 with SP2 or later These steps set the IP address and netmask the preferred primary comm path and the network polling of the CK721 A which are required for communicatio...

Page 15: ...LAN setting which specifies the frequency in seconds that the CK721 A panel polls the P2000 server during LAN connections The recommended value is 30 seconds The Network Polling Dup value is not curr...

Page 16: ...ondary IP interface Primary Host IP Address User Def The primary IP address used by the primary server network interface An IP address is a 32 bit number that is notated by using four numbers from 0 t...

Page 17: ...1 A 1 Periodically check the continuity of the grounding circuit 2 Perform operational testing monthly check for proper operation 3 Replace the lithium battery every five years or after extended five...

Page 18: ...Impaired Performance Conditions A list of conditions that may cause impaired performance is provided in the following table with reference pages Field Servicing Troubleshoot the CK721 A by substitutin...

Page 19: ...We welcome your comments at BE techpubs security jci com Security Solutions 805 522 5555 www johnsoncontrols com...

Reviews: