CK721-A Network Controller

Hardware Installation 

24-10025-237 Rev. – 

 

7

Chain Module Wiring

When connecting more than one module, wire the modules in parallel following the “daisy 
chain” pattern. Only the S300-DIN-L enclosure provides enough space for multiple modules 
and chain module wiring.

Cable Routing

The cables should run in grounded conduit or at least two feet from AC power, fluorescent 
lights, or other high energy sources.

I

MPORTANT

All data cables should be physically separated from power lines. If conduit is used, do not 

run data cables in the same conduit as power cables or certain door strike cables, e.g. strike voltage 
greater that 42V or Magnetic door locks without EMI suppression.

Every unit in a Johnson Controls installation must have its chassis bonded to a verified electrical 
ground (earth). In all cases, the local wiring codes apply.

The National Electrical Code NFPA 70 must be followed for installations in the USA. 

The Canadian Electric Code, C22.1 must be followed for installations in Canada.

BSI Standard BS7671 (latest edition) must be followed for installations in Great Britain. 
Additional information is given in the Cardkey Installers’ Code of Practice.

Conduit ground, cold water pipes, unbrazed joints, or dissimilar metals are unacceptable in the 
path of either building or supplement ground. Where grounding is required, connect only to the 
proven building electrical system ground (earth).

Chassis Grounding

Proper grounding of the S300-DIN-L enclosure is essential for the protection of electronic 
components against electrostatic discharge. A ground wire, 18 AWG minimum, must be run 
from the dedicated ground stud inside the enclosure to the building’s electrical ground. The 
dedicated ground stud is marked with the symbol

.

N

OTE

Cold water pipe is not an acceptable ground due to common use of non-conductive plastic pipe.

+24 VDC Connector

The CK721-A is provided with a pre-wired power connector. Depending on how the CK721-A 
is installed you may or may not need to use this connector.

Figure 5: +24 VDC Connector (Part of the DC Power Harness)

Power Wiring

For power wiring in the small enclosure, use the cable assembly provided with the small 
enclosure. Do not use the pre-wired power connector provided with the CK721-A.

COM

+24 VDC

COM

HOT

Summary of Contents for CK721-A

Page 1: ...24 10025 237 Revision December 2017 CK721 A Network Controller hardware installation manual...

Page 2: ...erial returns contact the branch if the material was purchased through a Johnson Controls branch or through the Product Sales Operations Team if ordered through the Advanced Order Management System AO...

Page 3: ...nt must be maintained between 13 35 C 55 95 F and relative humidity of 85 5 by the HVAC system Twenty four hour standby power shall be provided for the HVAC system 6 The installer shall incorporate a...

Page 4: ......

Page 5: ...rds and 8 000 off line transactions Note When the number of badges exceeds 120 000 the number of access groups should be limited to 50 000 All CK721 A panels are connected to the server via a 10 100Ba...

Page 6: ...cate 2398 cryptographic module version 2 0 9 from the Open Source Software Institute http www oss institute org CK721 A controller peer to peer User Datagram Protocol UDP broadcast messages are not en...

Page 7: ...g CK721 A to a Terminal Emulator RS232 Serial Null Modem Cable Wiring on page 6 RS232 B KONE serial server elevator or OTIS serial server elevator controller communications port or ThyssenKrupp serial...

Page 8: ...power is not supplied before you remove the lithium battery the realtime clock will be incorrect LEDs POWER ON is steady when power is applied FAULT OFF indicates normal operation ON indicates a gener...

Page 9: ...l and snap on To remove a module pull the white clips two are located at the bottom and one on top of the module then pull the bottom of the module out and lift it up Wiring Between RS485B and the Fie...

Page 10: ...Listed 22 AWG Stranded Hook up wire Limited to within cabinet Listed 18 AWG 3 cond stranded shielded 4000 ft 1215 m All modules connected to a single CK721 A panel must be within 4000 feet of the pan...

Page 11: ...71 latest edition must be followed for installations in Great Britain Additional information is given in the Cardkey Installers Code of Practice Conduit ground cold water pipes unbrazed joints or diss...

Page 12: ...tant Notes As a security precaution Johnson Controls strongly suggests changing the default controller password during the installation process The CK721 A panel must be set up first using Terminal Em...

Page 13: ...you will be following Serial cable between RS232C A J3 of the CK721 A controller and your laptop or PC serial port or Ethernet cable 2 Start your terminal emulator software 3 For serial communication...

Page 14: ...2000 server Version 3 8 Build 57 with SP2 or later These steps set the IP address and netmask the preferred primary comm path and the network polling of the CK721 A which are required for communicatio...

Page 15: ...LAN setting which specifies the frequency in seconds that the CK721 A panel polls the P2000 server during LAN connections The recommended value is 30 seconds The Network Polling Dup value is not curr...

Page 16: ...ondary IP interface Primary Host IP Address User Def The primary IP address used by the primary server network interface An IP address is a 32 bit number that is notated by using four numbers from 0 t...

Page 17: ...1 A 1 Periodically check the continuity of the grounding circuit 2 Perform operational testing monthly check for proper operation 3 Replace the lithium battery every five years or after extended five...

Page 18: ...Impaired Performance Conditions A list of conditions that may cause impaired performance is provided in the following table with reference pages Field Servicing Troubleshoot the CK721 A by substitutin...

Page 19: ...We welcome your comments at BE techpubs security jci com Security Solutions 805 522 5555 www johnsoncontrols com...

Reviews: