CK721-A Network Controller

Hardware Installation

24-10025-237 Rev. –

 

12

Panel Screen

The Panel screen is used when the CK721-A panel is configured for the P2000 server.

Router Configuration

The default CK721-A Panel Routing Information Protocol (RIP) is dynamic: it regularly listens 
for RIP from the network. If RIP is disabled, add route information manually. You must define 
both a 

Gateway

 IP address (which is the closest route to the panel) and a 

Destination

 IP address 

(which is the Server IP or Network IP). You can enter a maximum of four addresses at a time. 

Table 7: Panel Screen Field Description

Field

Type

Description

Panel Name

User Def.

The panel name is defined at the server, and then downloaded from the server to 
the panel. The panel name cannot be changed from the panel. 

Controller 
Primary 
IP Address

User Def.

The IP address used by the onboard network interface. An IP address is a 32-bit 
number that is notated by using four numbers from 0 through 255, separated by 
periods. To clean the IP entry, enter the IP value of 000.000.000.000.

Controller 
Primary 
IP Netmask

User Def.

A 32-bit number that is notated by using four numbers from 0 through 255, 
separated by periods. Typically, default subnet mask numbers use either 0 or 255 
as values. Default value: 255.255.255.0 [Class C networks]

Controller 
Secondary 
IP Address

User Def.

This IP address is reserved for future use in support of a secondary IP interface. 

Controller 
Secondary 
IP Netmask

User Def.

This netmask is reserved for future use in support of a secondary IP interface. 

Primary Host 
IP Address

User Def.

The primary IP address used by the primary server network interface. An IP 
address is a 32-bit number that is notated by using four numbers from 0 through 
255, separated by periods. To clean the IP entry, enter the IP value of 
000.000.000.000.

Note: 

Prior to entering the address, the panel must be defined in the P2000 

database.

Alternate Host 
IP Address

User Def.

This IP address is reserved for future use in support of a secondary IP interface. 

Preferred 
Primary
Comm Path

Toggle

Enabled (

Y

) by default. The CK721-A will communicate via onboard network 

interface.

Network Polling 
(LAN)

User Def.

Specifies the maximum time (in seconds) the panel allows between consecutive 
polls to the server over the LAN connection. The network poll (LAN) interval is 
limited to values between 5 seconds and 30 days.

Network Polling 
(Dup)

User Def.

The Dialup connection polling is not currently used.

Download Port 
Number (1 to 
65535)

User Def.

A TCP port number used for downloads from the server. This number must match 
that configured at the server. See 

step 6

 on 

page 11

 for details.

Upload Port 
Number (1 to 
65535)

User Def.

A TCP port number used for uploads to the server. This number must match that 
configured at the server. See 

step 6

 on 

page 11

 for details.

Priority Port 
Number (1 to 
65535)

User Def.

A TCP port number used for sending central access requests and for transactions 
confirming the panel and the server are online. This number must match that 
configured at the server. See 

step 6

 on 

page 11

 for details.

RS485 Baud 
Rate

Toggle

Selects the baud at which CK721-A to communicate with the terminals: 
• 9 (9,600 baud)
• 1 (19,200 baud)
• 3 (38,400 baud)*
* Recommended for OSDP and FICAM integrations.

Summary of Contents for CK721-A

Page 1: ...24 10025 237 Revision December 2017 CK721 A Network Controller hardware installation manual...

Page 2: ...erial returns contact the branch if the material was purchased through a Johnson Controls branch or through the Product Sales Operations Team if ordered through the Advanced Order Management System AO...

Page 3: ...nt must be maintained between 13 35 C 55 95 F and relative humidity of 85 5 by the HVAC system Twenty four hour standby power shall be provided for the HVAC system 6 The installer shall incorporate a...

Page 4: ......

Page 5: ...rds and 8 000 off line transactions Note When the number of badges exceeds 120 000 the number of access groups should be limited to 50 000 All CK721 A panels are connected to the server via a 10 100Ba...

Page 6: ...cate 2398 cryptographic module version 2 0 9 from the Open Source Software Institute http www oss institute org CK721 A controller peer to peer User Datagram Protocol UDP broadcast messages are not en...

Page 7: ...g CK721 A to a Terminal Emulator RS232 Serial Null Modem Cable Wiring on page 6 RS232 B KONE serial server elevator or OTIS serial server elevator controller communications port or ThyssenKrupp serial...

Page 8: ...power is not supplied before you remove the lithium battery the realtime clock will be incorrect LEDs POWER ON is steady when power is applied FAULT OFF indicates normal operation ON indicates a gener...

Page 9: ...l and snap on To remove a module pull the white clips two are located at the bottom and one on top of the module then pull the bottom of the module out and lift it up Wiring Between RS485B and the Fie...

Page 10: ...Listed 22 AWG Stranded Hook up wire Limited to within cabinet Listed 18 AWG 3 cond stranded shielded 4000 ft 1215 m All modules connected to a single CK721 A panel must be within 4000 feet of the pan...

Page 11: ...71 latest edition must be followed for installations in Great Britain Additional information is given in the Cardkey Installers Code of Practice Conduit ground cold water pipes unbrazed joints or diss...

Page 12: ...tant Notes As a security precaution Johnson Controls strongly suggests changing the default controller password during the installation process The CK721 A panel must be set up first using Terminal Em...

Page 13: ...you will be following Serial cable between RS232C A J3 of the CK721 A controller and your laptop or PC serial port or Ethernet cable 2 Start your terminal emulator software 3 For serial communication...

Page 14: ...2000 server Version 3 8 Build 57 with SP2 or later These steps set the IP address and netmask the preferred primary comm path and the network polling of the CK721 A which are required for communicatio...

Page 15: ...LAN setting which specifies the frequency in seconds that the CK721 A panel polls the P2000 server during LAN connections The recommended value is 30 seconds The Network Polling Dup value is not curr...

Page 16: ...ondary IP interface Primary Host IP Address User Def The primary IP address used by the primary server network interface An IP address is a 32 bit number that is notated by using four numbers from 0 t...

Page 17: ...1 A 1 Periodically check the continuity of the grounding circuit 2 Perform operational testing monthly check for proper operation 3 Replace the lithium battery every five years or after extended five...

Page 18: ...Impaired Performance Conditions A list of conditions that may cause impaired performance is provided in the following table with reference pages Field Servicing Troubleshoot the CK721 A by substitutin...

Page 19: ...We welcome your comments at BE techpubs security jci com Security Solutions 805 522 5555 www johnsoncontrols com...

Reviews: