PMGB0406B rev.1
70
(5) Refrigerant Cycle No. Setting (RSW2 & DSW5)
This setting is required. The unit arrives with all
settings in the OFF position.
(7) Fuse Recover (DSW7)
* Factory Setting
* In the case of applying high voltage to the terminal 1 and 2 of TB2,
the 0.5A fuse on the PCB is cut. In such a case,
¿
rst reconnect the
wirings correctly to TB2, and then set the No.1 pin to ON.
1
2
ON
OFF
1
2
ON
OFF
3
4
1
0
8
9
2
56
7
3
4
1
0
8
9
2
56
7
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
DSW5 (Tens Digit)
Refrigerant Cycle No. Setting
RSW2 (Units Digit)
Setting
Position
Set by inserting
slotted screwdriver
into the groove.
Ex.) Set at No.5 Cycle
DSW5
RSW2
Set All Pins OFF
Set at "5"
Before shipment, DSW5 and RSW2 are set at "0".
For the units supporting H-LINK II,
the ref. cycle No. can be set for Max. 64 cycles.
(No. 0~63)
Turn OFF all power supply of the DX-Kit and the outdoor units before DIP switch settings.
Otherwise, the setting will be invalidated and not take effect.
NOTES:
Ɣ
The “
Ŷ
” mark indicates setting for DIP switches. Figures show setting before shipment.
Ɣ
When the unit number and the refrigerant cycle are set, record the unit number and refrigerant cycle to
facilitate service and maintenance thereafter.
NOTICE
Each function can be selected with the wired controller. Refer to the “Installation and Maintenance Manual”
for the wired controller and the “Engineering Manual” for details.
< Circulator Function at Heating Thermo-OFF >
This function maintains fan operation by the set air
À
ow volume at the heating Thermo-OFF.
It improves temperature distribution when the unit is mounted on a high ceiling.
(8) Optional (DSW8)
No setting is required. This is for setting the model code of the DX-Kit.
1 2 3
ON
OFF
Figure 47. Refrigerant Cycle Setting
21.6 Function Selection by Wired Controller
(6) Unit Model Code Setting (DSW4)
No setting is required. This is for setting the
model code of the Dx-Kit.
(Ins)DX-Kit̲4e-rev1.indd 70
(Ins)DX-Kit̲4e-rev1.indd 70
2016/11/25 15:33:06
2016/11/25 15:33:06