PMGB0406B rev.1
27
Air
Handler
Models
Heater Models
1
Total
Heater
Amp@
240V
Min. Circuit Ampacity
MOP
2
208V
230V
208V
230V
Circuit
Circuit
1st2
2nd
1st2
2nd
1st2 2nd
1st2
2nd
36B
6HK46502025
46.2
28.3
25.0
30.9
27.6
30
25
35
30
48C
6HK46502025
46.2
28.6
25.0
31.3
27.6
30
25
35
30
48D
6HK46502025
46.2
28.6
25.0
31.3
27.6
30
25
35
30
6HK46502525
57.7
34.9
31.3
38.2
34.6
35
35
40
35
60D
6HK46502025
46.2
30.1
25.0
32.8
27.6
35
25
35
30
6HK46502525
57.7
36.4
31.3
39.7
34.6
40
35
40
35
1.
The 20kW and 25kW heater models (6HK46502025 and 6HK46502525) come with service
disconnects standard.
2.
MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
The 1st circuit includes blower motor amps. Refer to your local codes to determine the correct wire size.
Table 10. Electrical Data For Multi-source Power Supply: 208/230-3-60