PMGB0406B rev.1
21
Models
Motor FLA
1
Minimum Circuit Ampacity
MOP
2
18B
1.1
1.4
15
24B
1.4
1.8
15
30B
2.3
2.9
15
36B
2.6
3.3
15
36C
2.2
2.8
15
48C/48D
2.9
3.6
15
60C/60D
4.1
5.1
15
Table 3. Electrical Data - Cooling Only
1.
FLA = Full Load Amps.
2. MOP = Maximum Overcurrent Protection device; must be HACR type service disconnect or time delay
fuse. Refer to local codes to determine the correct wire size.
Table 4. Electrical Heat - Minimum Fan Speed
Heater Kit
Models
1,
2, 3
Nom.
kW@240V
Air Handler Models
18B
24B
30B
36B
36C
48C
48D
60C
60D
6HK(0,1)6500206
2.4kW
Med
Low
Low
Low
Low
Low
Low
Low
Low
6HK(0,1)6500506
4.8kW
Med
Low
Low
Low
Low
Low
Low
Low
Low
6HK(0,1)6500806
7.7kW
–
–
Med
Low
Low
Low
Low
Low
Low
6HK(0,1)6501006
6HK36501025
9.6kW
–
–
Med
Low
Low
Low
Low
Low
Low
6HK(1,2)6501306
12.5kW
–
–
Med
Low
Med
Low
Low
Low
Low
6HK(1,2)6501506
6HK36501525
14.4kW
–
–
Med
Low
Med
Low
Low
Low
Low
6HK(1,2)6501806
6HK36501825
17.3kW
–
–
–
Low
Med
Low
Low
Low
Low
6HK(1,2)6502006
6HK46502025
19.2kW
–
–
–
Low
–
Med
Med
–
Med
6HK(1,2)6502506
6HK46502525
24kW
–
–
–
–
–
–
Med
–
Med
1. (0,1) - 0 = no service disconnect OR 1 = with service disconnect.
2. (1,2) - 1 = with service disconnect, no breaker jumper bar OR 2 = with service disconnect & breaker
jumper bar.
3. 6HK3 = 3-Phase with terminal block connectors only, 6HK4 = 3-Phase with service disconnect.
Table 5. KW & MBH Conversions - For Total Power Input Requirement
For a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH
data from the table by the conversion factor in the following table.
DISTRIBUTION POWER
NOMINAL VOLTAGE
CONVERSION FACTOR
208V
240V
0.75
220V
240V
0.84
230V
240V
0.92