PMGB0406B rev.1
24
Air Handler
Models
Heater Models
1,2
Heater Amps
@240V
Field Wiring
Min. Circuit
Ampacity
MOP
3
208V
230V
208V
230V
48C
6HK(0,1)6500206
10
14.4
15.6
15
20
6HK(0,1)6500506
20
25.3
27.5
30
30
6HK(0,1)6500806
32
38.5
42.2
40
45
6HK(0,1)6501006
40
46.9
51.5
50
60
6HK(1,2)6501306
52
60.1
66.1
70
70
6HK(1,2)6501506
60
68.5
75.4
70
80
6HK(1,2)6501806
72
81.8
90.0
90
90
6HK(1,2)6502006
80
90.2
99.3
90
100
48D
6HK(0,1)6500206
10
14.4
15.6
15
20
6HK(0,1)6500506
20
25.3
27.5
30
30
6HK(0,1)6500806
32
38.5
42.2
40
45
6HK(0,1)6501006
40
46.9
51.5
50
60
6HK(1,2)6501306
52
60.1
66.1
70
70
6HK(1,2)6501506
60
68.5
75.4
70
80
6HK(1,2)6501806
72
81.8
90.0
90
90
6HK(1,2)6502006
80
90.2
99.3
100
100
6HK(1,2)6502506
100
111.8
123.2
125
125
60C
6HK(0,1)6500206
10
15.9
17.1
20
20
6HK(0,1)6500506
20
26.8
29.0
30
30
6HK(0,1)6500806
32
40.0
43.7
40
45
6HK(0,1)6501006
40
48.4
53.0
50
60
6HK(1,2)6501306
52
61.6
67.6
70
70
6HK(1,2)6501506
60
70.0
76.9
70
80
6HK(1,2)6501806
72
83.3
91.5
90
100
60D
6HK(0,1)6500206
10
15.9
17.1
20
20
6HK(0,1)6500506
20
26.8
29.0
30
30
6HK(0,1)6500806
32
40.0
43.7
40
45
6HK(0,1)6501006
40
48.4
53.0
50
60
6HK(1,2)6501306
52
61.6
67.6
70
70
6HK(1,2)6501506
60
70.0
76.9
70
80
6HK(1,2)6501806
72
83.3
91.5
90
100
6HK(1,2)6502006
80
91.7
100.8
100
110
6HK(1,2)6502506
100
113.3
124.7
125
125
1. (0,1) - maybe 0 (no service disconnect) or 1 (with service disconnect).
2. (1,2) maybe 1 (with service disconnect, no breaker jumper bar) or 2 (with service disconnect & breaker
jumper bar).
3. MOP = Maximum Overcurrent Protection device; must be HACR type service disconnect or time delay
fuse. Refer to your local codes to determine the correct wire size.
(Ins)DX-Kit̲4e-rev1.indd C-24
(Ins)DX-Kit̲4e-rev1.indd C-24
2016/11/25 15:32:46
2016/11/25 15:32:46