Do not touch or adjust any safety devices inside the indoor or outdoor units. All safety features,
disengagement, and interlocks must be in place and functioning correctly before the equipment is put
into operation. If these devices are improperly adjusted or tampered with in any way, a serious accident
can occur. Never bypass or jump-out any safety device or switch.
Ɣ
Before servicing, turn-OFF the power supply and use accepted lockout and tag out procedures at all
main switches.
Ɣ
This unit is the pressurized system. Never loosen threaded joints while the system is under pressure
and never open pressurized system parts.
Ɣ
Johnson Controls will not assume any liability for injuries or damage caused by not following steps
outlined or described in this manual. Unauthorized modi
¿
cations to Johnson Controls products are
prohibited as they…
ƕ
May create hazards which could result in death, serious injury or equipment damage;
ƕ
Will void product warranties;
ƕ
May invalidate product regulatory certi
¿
cations;
ƕ
May violate OSHA standards.
Take the following precautions to reduce the risk of property damage.
Ɣ
Be careful that moisture, dust, or variant refrigerant compounds not enter the refrigerant cycle during
installation work. Foreign matter could damage internal components or cause blockages.
Ɣ
If air
¿
lters are required on this unit, do not operate the unit without the air
¿
lter set in place. If the air
¿
lter is not installed, dust may accumulate and breakdown may result.
Ɣ
Do not install this unit in any place where silicon gases can coalesce. If the silicon gas molecules attach
themselves to the surface of the heat exchanger, the
¿
nned surfaces will repel water. As a result, any
amount of drainage moisture condensate can over
À
ow from the drain pan and could run inside of the
control box, possibly causing electrical failures.
Ɣ
When installing the unit in a hospital or other facility where electromagnetic waves are generated
from nearby medical and/or electronic devices, be prepared for noise and electronic interference
Electromagnetic Interference (EMI). Do not install where the waves can directly radiate into the control
box, controller cable, or controller. Inverters, appliances, high-frequency medical equipment, and radio
communications equipment may cause the unit to malfunction. The operation of the unit may also
adversely affect these same devices. Install the unit at least 10 ft. (3m) away from such devices.
Ɣ
When a wireless controller is used, locate at a distance of at least 3.3 ft. (1m) between this product and
electric lighting. If not, the receiver part of the unit may have dif
¿
culty receiving operation commands.
Ɣ
Do not install the unit in any location where animals and plants can come into direct contact with the
outlet air stream. Exposure could adversely affect the animals and plants.
Ɣ
Do not install the unit with any downward slope to the side of the drain adaptor. If you do, you may have
drain water
À
owing back which may cause leaks.
Ɣ
Be sure the drain hose discharges water properly. If connected incorrectly, it may cause leaks.
Ɣ
Do not install the unit in any place where oil can seep onto the units, such as table or seating areas in
restaurants, and so forth. For these locations or social venues, use specialized units with oil-resistant
features built into them. In addition, use a specialized ceiling fan designed for restaurant use. These
specialized oil-resistant units can be ordered for such applications. However, in places where large
quantities of oil can splash onto the unit, such as a factory, even the specialized units cannot be used.
These products should not be installed in such locations.