PMGB0406B rev.1
56
Figure 30. Attaching Cable Holders to Air Handler
Cable Holder for
Air Inlet Thermistor
Cable Holder for
Air Outlet Thermistor
Position
of Cable Holder
for Gathering and
Securing Excess Wiring
HI
MED
LO
1
/
1
32 to
1
/
16
(0.6 to 1)
1
/
2
(12)
Cable Holder
2-
3
/
4
to 4-
5
/
16
(70 to 110)
Cable Clamp
Ø
1
/
4
(6)
Thermistor
For Air Inlet and Air Outlet Thermistors
Thickness of Cable Holder
(1) Remove the upper front panel of the air handler to access the blower compartment.
(2) Remove the lower front panel of the air handler to access the coil compartment.
(3) Attach the cable holder for the air inlet thermistor at the air inlet side inside the air handler using the
screw already attached to the unit.
(4) Attach the cable holder of the air outlet thermistor on the fan casing inside the air handler using the
#8 (M5) tapping screw, thread length must not exceed 3/8 inch (10mm).
(5) Attach the cable holders for the securing wires using the screw already attached to the unit.
Secure the wiring neatly with the cable holders and cable clamps and make sure that the wiring will not be
held down by the covers.
Otherwise, the wiring may be damaged and serious accident and malfunction of the air handler may result.
21.4.2 Wiring Holes of Air Handler.
Make sure there are no shavings left inside the control box and air handler from opening the knock-out hole on the
air handler. Otherwise, it will cause serious accident and will cause corrosion to the heat exchanger.
Use the wiring holes of air handler indicated below for routing the wiring and cable from DX-Kit Control Box into air
handler.
Open the knock-out hole by using a punch or screwdriver and lightly tap near the edges of the knockout piece to
work it loose. It can then be removed.
The location is shown below of the wire holes of the air handler that are used to route the wiring and cables
from the DX-Kit control box.