PMGB0406B rev.1
28
Models
Wired Controller
Indication
(Blower Speed)
External Static Pressure (in. wc.)
0.10
0.20
0.30
0.40
0.50
0.60
0.70
208 Volts
18B
2
High (High)
723
702
666
576
N/A
N/A
N/A
Low (Medium)
566
543
480
382
N/A
N/A
N/A
24B
High (High)
990
973
953
924
885
797
713
Low (Medium)
736
723
703
644
606
540
457
30B
High (High)
1228
1192
1134
1078
1023
951
843
Low (Medium)
1023
998
958
915
859
741
677
36B
High (High)
1522
1475
1416
1349
1276
1188
1108
Low (Medium)
1251
1217
1180
1135
1085
1042
968
36C
High (High)
1539
1489
1450
1400
1283
1201
1110
Low (Medium)
1159
1147
1096
1042
994
943
877
48C
High (High)
1686
1643
1583
1507
1441
1357
1062
Low (Medium)
1482
1439
1392
1340
1280
1090
971
48D
High (High)
1988
1931
1853
1775
1695
1606
1391
Low (Medium)
1672
1636
1587
1522
1439
1302
1139
60C
2
High (High)
1851
1813
1757
1680
N/A
N/A
N/A
Low (Medium)
1718
1687
1631
1562
N/A
N/A
N/A
60D
2
High (High)
1932
1871
1784
1701
N/A
N/A
N/A
Low (Medium)
1795
1734
1660
1590
N/A
N/A
N/A
230 Volts
18B
2
High (High)
806
780
745
687
N/A
N/A
N/A
Low (Medium)
640
614
563
500
N/A
N/A
N/A
24B
High (High)
1142
1114
1078
1051
988
931
778
Low (Medium)
854
840
826
800
738
688
605
30B
High (High)
1316
1270
1213
1151
1081
1008
917
Low (Medium)
1139
1104
1059
1005
952
880
769
36B
High (High)
1601
1552
1485
1414
1337
1258
1178
Low (Medium)
1385
1352
1302
1252
1193
1106
1057
36C
High (High)
1671
1636
1581
1513
1439
1330
1210
Low (Medium)
1326
1310
1280
1238
1162
1081
994
48C
High (High)
1775
1727
1668
1596
1513
1431
1190
Low (Medium)
1591
1551
1500
1447
1380
1312
1059
48D
High (High)
2150
2069
1988
1894
1812
1690
1481
Low (Medium)
1878
1812
1752
1677
1604
1497
1258
60C
2
High (High)
1931
1889
1808
1739
N/A
N/A
N/A
Low (Medium)
1845
1798
1731
1659
N/A
N/A
N/A
60D
2
High (High)
2040
1969
1885
1779
N/A
N/A
N/A
Low (Medium)
1917
1861
1779
1694
N/A
N/A
N/A
1. Air handler units have been tested to UL 1995 / CSA 22.2 standards up to 0.30" wc external static pres-
sure. Dry coil conditions only, tested without
¿
lters. For optimal performance, external static pressures of
0.2" to 0.5" are recommended. Applications above 0.5" are not recommended.
2. Model 18B, 60C, and 60D air handlers must be used within external static pressure of 0.4".
Table 11. Air Flow Data (CFM