PMGB0406B rev.1
25
Table 8. Electrical Data For Multi-source Power Supply: 208/230-1-60
Air Handler
Models
Heater
Models
Total
Heater
Amp@
240V
Min. Circuit Ampacity
MOP*
208V
230V
208V
230V
Circuit
Circuit
1st* 2nd 3rd
1st* 2nd 3rd 1st* 2nd 3rd 1st* 2nd 3rd
30B
6HK16501306
52
21.7 37.6 –
23.6 41.5
–
25
40
–
25
45
–
6HK16501506
60
24.5 43.3 –
26.8 47.9
–
25
45
–
30
50
–
36B
6HK16501306
52
22.0 37.6 –
24.0 41.5
–
25
40
–
25
45
–
6HK16501506
60
24.9 43.3 –
27.2 47.9
–
25
45
–
30
50
–
6HK16501806
72
42.3 39.0 –
46.4 43.1
–
45
40
–
50
45
–
6HK16502006
80
46.6 43.3 –
51.2 47.9
–
50
45
–
60
50
–
36C
6HK16501306
52
21.5 37.6 –
23.5 41.5
–
25
40
–
25
45
–
6HK16501506
60
24.4 43.3 –
26.7 47.9
–
25
45
–
30
50
–
6HK16501806
72
41.8 39.0 –
45.9 43.1
–
45
40
–
50
45
–
48C
6HK16501306
52
22.4 37.6 –
24.4 41.5
–
25
40
–
25
45
–
6HK16501506
60
25.3 43.3 –
27.6 47.9
–
30
45
–
30
50
–
6HK16501806
72
42.6 39.0 –
46.8 43.1
–
45
40
–
50
45
–
6HK16502006
80
47.0 43.3 –
51.5 47.9
–
50
45
–
60
50
–
48D
6HK16501306
52
22.4 37.6 –
24.4 41.5
–
25
40
–
25
45
–
6HK16501506
60
25.3 43.3 –
27.6 47.9
–
30
45
–
30
50
–
6HK16501806
72
42.6 39.0 –
46.8 43.1
–
45
40
–
50
45
–
6HK16502006
80
47.0 43.3 –
51.5 47.9
–
50
45
–
60
50
–
6HK16502506
100
47.0 43.3 21.7 51.5 59.9 24.0 50
45
25
60
60
25
60C
6HK16501306
52
23.9 37.6 –
25.9 41.5
–
25
40
–
30
45
–
6HK16501506
60
26.8 43.3 –
29.1 47.9
–
30
45
–
30
50
–
6HK16501806
72
44.1 39.0 –
48.3 43.1
–
45
40
–
50
45
–
60D
6HK16501306
52
23.9 37.6 –
25.9 41.5
–
25
40
–
30
45
–
6HK16501506
60
26.8 43.3 –
29.1 47.9
–
30
45
–
30
50
–
6HK16501806
72
44.1 39.0 –
48.3 43.1
–
45
40
–
50
45
–
6HK16502006
80
48.5 43.3 –
53.0 47.9
–
50
45
–
60
50
–
6HK16502506
100
48.5 43.3 21.7 53.0 59.9 24.0 50
45
25
60
60
25
*
MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
The 1st circuit includes blower motor amps. Refer to your local codes to determine the correct wire size.