ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
OVEN
kW
APPROX. AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
REVERSING
208
3ø
3
20
61
—
80
220
3ø
3
17
50
51
70
240
3ø
3
20
54
—
70
380
3ø
3
17
31
—
40
460
3ø
3
18.5
26
—
40
480
3ø
3
20
27
—
40
208
3ø
3
24
72
—
90
220
3ø
3
20
58
59
80
240
3ø
3
24
63
—
80
380
3ø
3
20
36
—
50
460
3ø
3
22
31
—
40
480
3ø
3
24
32
—
50
575
3ø
3
24
27
—
40
208
3ø
3
30
88
—
125
220
3ø
3
26
73
75
100
240
3ø
3
30
78
—
100
380
3ø
3
26
45
—
60
460
3ø
3
28
38
—
50
480
3ø
3
30
39
—
50
575
3ø
3
30
33
—
50
230
3ø
3
18.5
—
53
70
240
3ø
3
20
—
56
80
380
3ø
4 or 3
17
—
29
40
400
3ø
4 or 3
18.5
—
30
40
416
3ø
4 or 3
20
—
31
40
230
3ø
3
22
—
61
80
240
3ø
3
24
—
65
90
380
3ø
4 or 3
20
—
34
50
400
3ø
4 or 3
22
—
35
50
416
3ø
4 or 3
24
—
37
50
440
3ø
4 or 3
20
—
29
40
230
3ø
3
28
—
76
100
240
3ø
3
30
—
80
125
380
3ø
4 or 3
26
—
43
60
400
3ø
4 or 3
28
—
44
60
416
3ø
4 or 3
30
—
45
60
3. Grounding
A ground (earth) connection
must be
provided and installed in accordance with state and local codes. In the
absence of these codes, grounding
must conform
to applicable requirements of the National Electrical Code
ANSI/NFPA NO. 70-LATEST EDITION, or in Canada, the installation
must conform
to applicable Canada
Standards: Canadian Electrical Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION. The ground
connection may be to a proven earth ground at the location service panel.
For added personal safety, when possible, it is suggested that a separate ground wire (size per local codes) be
connected from the ground connection of the dryer to a grounded cold water pipe.
DO NOT ground to a gas
pipe or hot water pipe
. The grounded cold water pipe must have
metal-to-metal connection
ALL
the way to
the electrical ground. If there are any nonmetallic interruptions, such as, a meter, pump, plastic, rubber, or
other insulating connectors, they
must be
jumped out with a wire (size per local codes) and securely clamped
to bare metal at both ends.
IMPORTANT:
For personal safety and proper operation, the dryer
must be
grounded.
Provisions are made for ground connection in each dryer at the electrical service connection area.
4. Electrical Connections
A wiring diagram is located inside the control box for connection data.
If local codes permit, power to the dryer can be made by the use of a flexible U.L. listed power cord/pigtail
(wire size
must conform
to rating of dryer), or the dryer can be hard wired directly to the service breaker
panel. In both cases, a strain relief
must be
installed where the wiring enters the dryer.
Check your national and local code for breaker and wire size
1/7/15