ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT
:
NOTES
: A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering, specify exact
voltage.
When fuses are used they must be dual element, time delay, current limiting, class
RK1 or RK5 ONLY. Calculate/determine correct fuse value, by applying either local
and/or National Electrical Codes to listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) type ONLY. For others,
calculate/verify correct breaker size according to appliance amp draw rating and
type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
OVEN
kW
APPROX. AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
NON-REVERSING
208
1ø
2
20
102
—
150
220
1ø
2
17
82
81
125
230
1ø
2
18.5
84
84
125
240
1ø
2
20
88
88
125
208
1ø
2
24
121
—
175
220
1ø
2
20
95
95
125
230
1ø
2
22
99
99
125
240
1ø
2
24
105
105
150
208
3ø
3
20
61
—
80
220
3ø
3
17
49
49
70
230
3ø
3
18.5
50
50
70
240
3ø
3
20
53
53
70
208
3ø
3
24
72
—
100
220
3ø
3
20
57
56
80
230
3ø
3
22
58
59
80
240
3ø
3
24
63
62
80
380
3ø
4
17
—
30
40
400
3ø
4
18.5
—
30
40
416
3ø
4
20
—
32
50
380
3ø
4
20
—
34
50
400
3ø
4
22
—
35
50
416
3ø
4
24
—
38
50
208
3ø
3
20
59
—
80
220
3ø
3
17
48
—
60
240
3ø
3
20
51
52
70
380
3ø
3
17
29
—
40
460
3ø
3
18.5
25
—
40
480
3ø
3
20
26
—
40
208
3ø
3
24
70
—
90
220
3ø
3
20
56
56
80
240
3ø
3
24
61
62
80
380
3ø
3
20
34
—
50
460
3ø
3
22
30
—
40
480
3ø
3
24
31
—
40
208
3ø
3
30
86
—
125
220
3ø
3
26
71
—
90
240
3ø
3
30
75
76
100
380
3ø
3
26
43
—
60
460
3ø
3
28
37
—
50
480
3ø
3
30
38
—
50
575
3ø
3
30
32
—
50
220
3ø
3
17
—
49
70
230
3ø
3
18.5
—
50
70
380
3ø
4 or 3
17
—
28
40
400
3ø
4 or 3
18.5
—
29
40
416
3ø
4 or 3
20
—
30
40
230
3ø
3
22
—
59
80
380
3ø
4 or 3
20
—
33
50
400
3ø
4 or 3
22
—
34
50
416
3ø
4 or 3
24
—
36
50
440
3ø
4 or 3
20
—
28
40
220
3ø
3
26
—
72
100
230
3ø
3
28
—
74
100
380
3ø
4 or 3
26
—
42
60
400
3ø
4 or 3
28
—
43
60
416
3ø
4 or 3
30
—
44
60
Check your national and local code for breaker and wire size
1/7/15
b. Electric Models Only
ALL
electrically heated dryers
must
be
connected to the electric service shown on the dryer’s data label.
The connecting wires
must be
properly sized to handle the rated current.