JetSym was used to set up a test scenario in which the setpoint switches back and forth between
0.3 A and 0.7 A.
Closed-loop control parameters: P=100,000, I=0, D=0, Measurements: blue=setpoint,
red=actual value
Fig. 10:
Test scenario with the control parameters P=100,000, I=0, D=0
The P controller works well with this value. However, the setpoint is not reached, which corre-
sponds to the typical behavior of a P controller (see
Current control with PID controller [
Closed-loop control parameters: P=100,000, I=5,000, D=0, Measurements: blue=setpoint,
red=actual value
Fig. 11:
Test scenario with the control parameters P=100,000, I=5,000, D=0