Jetter AG
Programming | 8
jxm-io-ew30_ba_2151_manual
37 / 56
Subindex type
Description
Typ
e
Type
of ac-
cess
Unit/
value range
64
MIN_CURRENT
If less current flows at the
output than the set threshold,
this is detected as a cable
break and the condition is set
in
Operational
state (as of
OS 2.05.0.00).
U16 R/W
1 mA
The default
value is the
minimum pos-
sible value:
■
PWMi-H3
outputs:
min. 200
mA
■
Other out-
puts: min.
500 mA
65
OPENCIRCUIT_
DETECTION
Enables/disables the cable
break detection of a port.
Mode 1
checks once during
boot whether a load pulls the
output to GND.
Mode 2
additionally checks
in the switched-on state
whether MIN_CURRENT has
been undershot.
U16 R/W
0 = No cable
break detec-
tion
1 = Cable
break detec-
tion only in
PREOPERA-
TIONAL
mode
2 = Perma-
nent cable
break detec-
tion
68
RESOLUTION
Resolution, e.g. at encoder
input
U8
R/W
0 … 2
0 =
1/4 resolution
1 =
1/2 resolution
2 =
Full resolution
Tab. 30:
IO interface parameters