HMCflex
Operating instructions
16/23
© ehb errors and omissions excepted
Operating instructions.doc
[4] glow times
temp1
Temp 1 gives a value for the temperature-dependent preheating. Higher or
lower value is automatically recognised by the management system by com-
paring temp 1 and temp 2. The management system determines the glow
times between the values in a linear way, depending on time temp 1 and time
temp 2. Where there are lower or higher temperatures, the glow time remains
constant according to time temp 1 or time temp 2.
temp2
Temp 2 gives the second value for the temperature-dependent preheating.
Higher or lower value is automatically recognised by the management system
by comparing temp 1 and temp 2. The management system determines the
glow times between the values in a linear way, depending on time temp 1 and
time temp 2.
time temp1
Gives the glow time for temp 1.
time temp2
Gives the glow time for temp 2.
afterglow
Gives the time period, during which the glow continues after start-up. The af-
terglow complies with the chosen multiples of the preheat time.
[5] altern.excita
period
The alternator excitement time can be set. Settings between 1 and 4 seconds
are possible.
[6] autostart
on/off
The autostart function can be switched on or off. When no auto boot is pro-
grammed, the signal output is on contact no. 7 of the connecting plug. Signal
output and auto boot cannot be operated in parallel.
The autostart input is positive-switching!!!
When the autostart is programmed, the "W" terminal or a proximity
switch must be connected!!!
pause
Time between two start-up attempts. 1 to 45 seconds can be programmed.
duration
Length of a start-up attempt. 1 to 45 seconds can be programmed.
RepEngSrart
Number of start-up attempts. 1 to 5 attempts can be programmed.
The autostart function can be deactivated by the user at any time. By using the arrow key
you access the daily operating hours / automatic / manual menu. You can then change between auto-
matic and manual operation using the SET key. This choice is also retained when the management
system is switched off.
[7] emergency
oil pressure
Monitoring of the oil pressure can be programmed as powering down (shutd),
warning (alarm), without monitoring (without) or as power down with cool down
time (Cdown).
temperature
Monitoring of the engine temperature (cylinder head temperature or coolant
temperature) can be programmed as powering down (shutd), warning (alarm),
without monitoring (without) or as power down with cool down time (Cdown).
D+
Monitoring of the charging voltage can be programmed as powering down
(shutd), warning (alarm), without monitoring (without) or as power down with
manually
daily hours: 0.0h
automatic
daily hours: 0.0h
Summary of Contents for A540 Di D-1703 EDR 80km/h
Page 2: ......
Page 4: ......
Page 6: ......
Page 8: ......
Page 10: ......
Page 12: ......
Page 14: ......
Page 44: ......
Page 46: ......
Page 71: ...Service Schedule...
Page 75: ...Original Ersatzteile Original spare parts Pi ces de rechange d origine...
Page 78: ......
Page 80: ......
Page 82: ......
Page 84: ......
Page 86: ......
Page 88: ......
Page 90: ......
Page 92: ......