Vapor Connection
✓
The best quality of the steam produced in the steam generator depends on the quality of the steam
installation in the process.
✓
The steam generator steam outlet valve size is given in the table below. The steam installation must
always be one dimension above the steam outlet diameter used. For example, if the main steam valve
of the steam generator is DN50, the steam installation should be DN65.
9
Model
SHS
250
SH
S
350
SHS
500
SHS
750
SHS
1000
SHS
1250
SHS
1500
SHS
1700
SHS
2000
SHS
2500
SHS
3000
DN
32
40
50
65
65
65
80
80
100
100
125
Vapor Connection Measurements According to Capacities
✓
In cases where more than one point of steam should be taken from steam generator, steam
distribution collector should be made.
Collecter Application Exemple
✓
The steam line from the steam generator to the
collector must be at least one diameter bigger than the
steam generator steam outlet size.
✓
The steam distribution collector must be at least two
diameters broader than the steam installation from the
steam generator to the collector.
✓
The condensate group should be used for the
condensate formed in the collector.
✓
In the steam installations, a slope of 5% should be given
towards the steam generator. This will prevent the water
from the line to advance into the process.