Water Softening Device Connection
✓
At the entrance of the water softener, there is a sediment filter, valve and manometer which
are left by the factory.
✓
The on-site connection is to connect the mains water to the valve on the inlet of the water
softener.
✓
A pipe fitting must be used when connecting the mains water to the device. A valve should be
installed at the outlet of the device to shut off the water if necessary and a sampling tap to take
samples from the outlet of the device.
✓
Following the connection of the mains water, the water softener must be fed with water and
the pressure fed from the pressure gauge left on the softener should be observed.
✓
Water softening devices require water and water pressure for regeneration. Inlet water
pressure must be min. 3 and max. 6 bars.
✓
If the mains water is not at the desired pressure, a storage tank and a booster must be
positioned to pressurize the water.
✓
If the water used is supplied from a source other than mains water (such as well water), the
water must be subjected to good filtration.
✓
A 220 V socket must be located near the water softener for the electrical supply.
✓
Water softening devices use a 12 V adapter for power supply. (Delivered with device.)
✓
Regeneration process in water softening devices is set at 02:00 at night. For this reason, the
220 V socket positioned for the water softener adapter must be set to provide electricity for 24
hours.
✓
During the regeneration, the water softener discharges the waste water from the outlet at the
rear of the device. This outlet should be connected to a drain.