✓
In the production of the smokestack, it is necessary to choose the diameter of the smokestack
according to the fuel to be used.
✓
Best possible production of the smokestack is necessary for the release of gas waste, for the burner
to burn in the effectively and for your vapor generator to function with the highest efficiency.
8
c
–
Smokestack Connection
Measurements of Opening of the Smokestack According to Capacities
Model
SHS
250
SHS
350
SHS
500
SHS
750
SHS
1000
SHS
1250
SHS
1500
SHS
1700
SHS
2000
SHS
2500
SHS
3000
mm Ø
170
170
280
300
350
350
400
400
400
450
450
✓
When connecting the steam generator smokestack outlet to the smokestack, the connection from
the generator to the smokestack must be provided with a 10% slope, which will facilitate the discharge
of the exhaust gas.
ÖRNEK
BACA BA
G
LANTISI
1000 mm
✓
When connecting the smokestack flanges, always use a leakproof and
non-flammable gasket.
✓
There must be two
½ ”size
sleeves on the smokestack. The first one is
required for smokestack gas temperature thermocouple, which provides
value to the smokestack temperature thermostat on the steam
generator electrical control panel, and the other is required to use the
smokestack gas analysis device.
✓
The dimensions of a smokestack depend on variables such as smoke
temperature, outside temperature, smokestack load and operating time.
The following formula can be applied for smokestack sizing.
Summary of Contents for SHS 1000
Page 10: ...Steam Distribution Connection Diagram 10 Buhar Da l m Kollekt r...
Page 12: ...Condensate Return Connection Diagram 12...
Page 15: ...15 Vent Connection and Blowdown Connection Diagram...
Page 55: ...55...
Page 56: ...56...