54
1 - Perform all weekly control and maintenance operations respectively.
JENESIS SHS SERIES STEAM GENERATOR MONTHLY CONTROL AND MAINTENANCE
2 - Empty the condensate tank to remove sediment, sludge and other deposits. Refill the
condensate tank.
Tank Cover
Tank with cover removed
Tank Blowdown Valve
3 - Clean the salt tank of the water softener. The
salt
dissolved
in
the
salt
tank
causes
contamination on the surface of the tank over
time. Empty the salt tank before cleaning the
tank. To disconnect the salt tank from the system,
first remove the valve connection fitting. Remove
the salt tank from the system by pulling it
towards you. After cleaning the salt tank, make
the connection by repeating the same procedure
and add enough salt and water to the salt tank.
Water Softening Device Salt Tank
Valve Connection
Summary of Contents for SHS 1000