Safety valve is located on the vapor generator vapor outlet separator section.
✓
When the pressure of the vapor generator passes the maximum operating pressure, safety
valve discharges the surplus vapor and releases it to outside.
✓
During the process of connections being done in place, safety valve should be taken to a dead
spot and outside where people cannot be harmed.
✓
Safety valve should be installed without making any links to another installation connections.
✓
If the present location is favorable, safety valve installation should be made with a slope
towards outside, with a straight pipe.
✓
If the safety valve installation cannot be linked to outside with a straight pipe and/or an
attachment material similar to elbow is being used; relief valve application must be used, as the
place in which these components are situated will be filled with water.
16
i
–
Safety Valve Connection
BUHAR ÇIKIŞ
SEPERATÖRÜ
EMNİYET
VENTİLİ
EMNİYET VENTİLİ TAHLİYE BORUSU