R-HDx
Read - Higher
Delay
Alarm + port
To get the delay time to activate the Upper
Temperature Alarm.
Replace the ‘x’ with the number of the destination
port in ASCII, for example “RHD1”.
The Data Field contains the delay time to activate the
Upper Temperature Alarm, expressed in seconds and
hundreds of seconds, according to:
“Format “ss.cc” in ASCII. “ss” corresponds to the
time in seconds, and “cc” corresponds to the time
in hundredths of a second. Example: “01.60” means
1,6s; “00.10” means 0,1s.
When the tip temperature is above the Upper
Temperature Alarm for a longer time than the delay set
in the HDx, the Alarm will be set to 1.”
The Data Field contains the Higher Delay Alarm.
“99999” means that the alarm is disabled.
Code
Description
Details
W-HDx
Write - Higher
Delay
Alarm + port
Sets the delay time to activate the Upper Temperature
Alarm. The delay time starts when the tip temperature
is above the value in HAx.
Replace the ‘x’ with the number of the destination
port in ASCII, for example “WHD1”.
The Data Field contains the delay time to activate the
Upper Temperature Alarm, expressed in seconds and
hundrets of seconds, according to:
Format “ss.cc” in ASCII. “ss” corresponds to the
time in seconds, and “cc” corresponds to the time in
hundreds of a second. Example: “01.60” means 1,6s;
“00.10” means 0.1s.
The JBC device responds with an “A-HDx”.
To disable the Hibernation mode, send “99999”.