Default value 0
.
0
Automatic energy
-
saving selection
P413
Setting Range
:
0
~
100 Unit
:
1
P413 Automatic energy
-
saving selection
In constant
-
speed running of automatic energy
-
saving selection
,
best voltage
value may be calculated by loading condition and provided to load
,
in order to
achieve best energy
-
saving
.
Attention
:
for running that load changes frequently or is almost at full load
,
this
function is not suitable
.
F
Default value 0
.
0
Restart after instant power off
P416
Setting Range
:
0
~
1 Unit
:
1
Explanation
:
0
:
Invalid
:
no restart after instant power failure
1
:
Valid
:
frequency tracing start
-
up
0
:
Invalid
Inverter clears the running command after power failure
.
After power is
recovered
,
inverter will not start automatically
.
1
:
Frequency tracing enable
When power is shut
-
off in short time
,
inverter keeps the running command as
effective
.
When power is recovered in time
,
inverter will tracing the motor speed
and resume output
.
Attention
:
when instant power failure restarting is enabled
,
inverter may start
the motor automatically
.
Please take care of the safety when use this function
.
6
Chapter 6 Description of parameter setting
FC100 Series User Manaul
Summary of Contents for FC100 Series
Page 9: ...9 Chapter 2 Storage and Installation ...
Page 12: ...12 ...
Page 13: ...13 Chapter 3 Wiring Diagram and Terminal Explanation ...
Page 20: ...20 ...
Page 21: ...21 Chapter 4 Keypad Operation ...
Page 24: ...24 4 ...
Page 25: ...25 Chapter 5 Function Parameters Table ...
Page 36: ...36 ...
Page 37: ...37 Chapter 6 DESCRIPTION OF PARAMETER SETTINGS ...