47
Procedure
Input
Explanation
1
K1 close
Reverse of inverter is started
2
(
K1 open
)
press stop key
Inverter stops
3
K1 open
Running signal is removed
4
K1 close
Reverse
of inverter is started
P104
Reverse prevention setting
Factory Setting
:
1
Setting
Range
:
0
-
1
Unit
:
1
Explanation
:
0
:
Reverse prohibited
1
:
Reverse allowed
Many devices only allow rotation in single direction
.
In this case
,
you can set the
machine in single rotation mode by this parameter
.
0
:
Reverse prohibited
Reverse of motor is prohibited
.
When P104 is set at reverse prohibited
,
switch
between Forward and reverse is invalid
.
1
:
Reverse allowed
Reverse of motor is enabled
,
switching between forward and reverse is valid
.
The output frequency range of inverter is 0
.
1
~
400
.
00Hz
.
Therefore
,
inverter can
drive the motor higher than 50
/
60Hz
,
which could cause mechanical damage or
accident
.
This parameter is to limit the inverter output frequency in order to prevent motor
operating at too higher speed
.
P105
Max
.
frequency
Factory Setting
:
50
.
0HZ
Setting
Range
:
0
-
400HZ
This parameter is to set the minimum output frequency of the inverter
.
If the
setting frequency is lower than the Min
.
frequency
,
inverter will output on the Min
.
frequency
.
In some application
,
this function could avoid motor overheating due
to the low speed operation
.
P106
Min
.
frequency
Factory Setting
:
0
.
00HZ
Setting
Range
:
0
-
400HZ
6
Chapter 6 Description of parameter setting
FC100 Series User Manaul
Summary of Contents for FC100 Series
Page 9: ...9 Chapter 2 Storage and Installation ...
Page 12: ...12 ...
Page 13: ...13 Chapter 3 Wiring Diagram and Terminal Explanation ...
Page 20: ...20 ...
Page 21: ...21 Chapter 4 Keypad Operation ...
Page 24: ...24 4 ...
Page 25: ...25 Chapter 5 Function Parameters Table ...
Page 36: ...36 ...
Page 37: ...37 Chapter 6 DESCRIPTION OF PARAMETER SETTINGS ...