7
)
Inverter may interfere with other devices
.
Causes and corrective actions
:
The input
/
output
(
main circuit
)
of the inverter includes high frequency components
,
which may interfere with the communication devices used near the inverter
.
In this
case
,
set EMC filter valid to minimize interference
.
a
:
Decrease carrier frequency
(
P115
).
b
:
Install a noise filter on the inverter output side to reduce the
electromagnetic nois generated from the inverter
.
c
:
Install a noise filter on the inverter input side
.
d
:
For reduction of induction noise from the power line of the
inverter
.
it is recommended to wire the earth cable by returning it to
the earth terminal of the inverter
.
e
:
To prevent a malfunction due to noise
,
keep the signal cables more than 10cm away
from the power cables
,
f
:
Control circuit cable should use shielded cable
,
and the
cable should be installed in metal tube
8
-
5 Inverter
-
generated noises and their reduction techniques
Some noises enter the inverter to malfunction it and others are radiated by the
inverter to malfunction peripheral devices
.
Though the inverter is designed to be
insusceptible to noises
,
it handles low
-
level signals
,
so it requires the fllowing basic
techniques
.
Also
,
since the inverter chops outputs at high carrier frequency
,
that
could generate noises
.
If these noises cause peripheral devices to malfunction
,
measures should be taken to suppress noises
.
These techniques differ slightly
depending on noise propagation paths
.
1
,
Basic techniques
• Do not run the power cables
(
I
/
O cables
)
and signal cables of the inverter in parallel
with each other and do not bundle them
.
• Use twisted pair shielded cables for the detector connection and control signal
cables
,
and connect the sheathes of the shield cables to terminal SC
.
• Earth the inverter
,
motor
,
etc
,
at one point
.
2
,
Techniques to reduce noises that enter and malfunction the inverter
When devices that generate many noises
(
which use magneticcontactors
,
magnetic
brakes
,
many relays
,
for example
)
are installed neat the inverter and the inverter
may be malfunctioned by noises
,
the following measures must be taken
:
Provide surge suppressors for devices that generate many noises to suppress
noises
.
• Fit data line filters to signal cables
.
• Earth the shields of the detector connection and control signal cables with Cable
clamp metal
.
8
107
Chapter 8 Troubleshooting and Fault Informatin
FC100 Series User Manaul
Summary of Contents for FC100 Series
Page 9: ...9 Chapter 2 Storage and Installation ...
Page 12: ...12 ...
Page 13: ...13 Chapter 3 Wiring Diagram and Terminal Explanation ...
Page 20: ...20 ...
Page 21: ...21 Chapter 4 Keypad Operation ...
Page 24: ...24 4 ...
Page 25: ...25 Chapter 5 Function Parameters Table ...
Page 36: ...36 ...
Page 37: ...37 Chapter 6 DESCRIPTION OF PARAMETER SETTINGS ...