49
Parameters from P109 to P114 determine the V
/
F curve of inverter
.
Set
corresponding V
/
F curves according to different loads
.
Constant torque curve
:
application for constant torque load
,
output voltage and output frequency are in
linear relation
.
Down
(
variable
)
torque curve
:
application for variable torque load
,
like fan and
pump
.
Load will increase with the increase of rotation speed
.
High start torque curve
:
application for heavy load and load need high starting
torque
.
P109
:
V
/
F maximum voltage
,
V
/
F maximum voltage can be set according to the
motor connected
.
Generally
,
it will be set at the rated voltage of motor
.
When
motor is very near to inverter
,
usually within 30m
,
it should be set at a higher
value
.
P110
:
V
/
F fundamental frequency
V
/
F fundamental frequency
,
please set it at the running voltage frequency of
motor
.
Generally
,
do not change V
/
F fundamental frequency setting
;
or else
,
it is
very likely to damage motor
.
P111
:
V
/
F intermediate voltage
Set V
/
F intermediate voltage according to the specific load
.
Improper setup can
cause over current of motor or insufficient torque output
,
or even cause inverter
protection
.
Increasing the value of P111 can increase output torque and output
current
.
Please monitor output current while changing the value of P111
.
While
changing the value of P111
,
adjust the value slowly until the necessary output
torque is reached
.
Too higher setting may cause inverter protection or fault
.
P112
:
V
/
F intermediate frequency
V
/
F intermediate frequency determines the intermediate point of V
/
F curve
.
Improper setup can cause insufficient torque or over current protection of
inverter
.
Generally
,
do not change the setup value of this parameter while using
.
6
Chapter 6 Description of parameter setting
FC100 Series User Manaul
Summary of Contents for FC100 Series
Page 9: ...9 Chapter 2 Storage and Installation ...
Page 12: ...12 ...
Page 13: ...13 Chapter 3 Wiring Diagram and Terminal Explanation ...
Page 20: ...20 ...
Page 21: ...21 Chapter 4 Keypad Operation ...
Page 24: ...24 4 ...
Page 25: ...25 Chapter 5 Function Parameters Table ...
Page 36: ...36 ...
Page 37: ...37 Chapter 6 DESCRIPTION OF PARAMETER SETTINGS ...